Use and Care Manual
Table Of Contents
- Foreword
- Safety Notice
- CONTENTS
- Safety Notice on Maintenance
- Safety Notice on Operation
- 1 Product Introduction
- NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
- 2 Control
- 3 Troubleshooting
- 3.1 Wiring Diagrams
- 3.2 PCB Layout
- 3.3 Error Code
- 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
- 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
- 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
- 3.4.4 “F2” Condenser Temperature Sensor Error
- 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
- 3.4.6 “F4” Discharge Temperature Sensor Error
- 3.4.7 “F6” ODU Tube Temperature Sensor Error
- 3.4.8“EE” ODU Memory Chip Error
- 3.4.9 “H4” Overload
- 3.4.10 “H5” IPM Protection
- 3.4.11 “H6” DC Fan Error
- 3.4.12 “H7” Driver Out-of-Step Protection
- 3.4.13 “HC” PFC Protection
- 3.4.14 “Lc” Startup Failure
- 3.4.15 “P0” Driver Reset Protection
- 3.4.16 “P5” Over-Current Protection
- 3.4.17 “P6” Master Control and Driver Communication Error
- 3.4.18 “P7” Driver Module Sensor Error
- 3.4.19 “P8” Driver Module High Temperature Protection
- 3.4.20 “PA” AC Current Protection
- 3.4.21 “Pc” Driver Current Error
- 3.4.22 “PL” Bus Low-Voltage Protection
- 3.4.23 “PH” Bus High-Voltage Protection
- 3.4.24 “PU” Charge Loop Error
- 3.4.25 “ee” Drive Memory Chip Error
- 3.5 Failures Not Caused by Errors
- 4 Maintenance
- Appendices
- 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
- 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
- 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
- 2 Temperature/Pressure List of Refrigerant
- 3 Operation Tools
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
22
3.3 Error Code
No.
Error code
Error
1
E1
Compressor high pressure protection
2
E3
Compressor low pressure protection
3
E4
Compressor air discharge high-temperature protection
4
F2
Condenser temperature sensor error
5
F3
Outdoor ambient temperature sensor error
6
F4
Discharge temperature sensor error
7
F6
ODU tube temperature sensor error
8
EE
ODU memory chip error
9
H4
Overload
10
H5
IPM protection
11
H6
DC fan error
12
H7
Driver out-of-step protection
13
HC
Pfc protection
14
Lc
Startup failure
15
P0
Driver reset protection
16
P5
Over-current protection
17
P6
Master control and driver communication error
18
P7
Driver module sensor error
19
P8
Driver module high temperature protection
20
PA
AC current protection
21
Pc
Driver current error
22
PL
Bus low-voltage protection
23
PH
Bus high-voltage protection
24
PU
Charge loop error
25
ee
Drive memory chip error
If malfunction occurs during operation, LCD temperature display zone will show the failure information. If
several malfunctions occur at the same time, their corresponding error codes will be shown in turn. When
malfunction occurs, please shut off the unit and send for professional personnel to repair. For example, E1 (as
shown below) indicates high pressure protection.










