How to Guide

Change the logic on the board from 3 ton to 2 ton
Instruction for Universal Series
Default capacity setting of outdoor unit GUD36W/A-D(U) is 36K, can adjust
the condenser main board dip switch to change to 24K. Instruction as below:
1. Please complete the capacity dip switch setting before you power on the
unit.
2. Capacity dip switch position of condenser main board is the red circle
below.
Condenser Main Board
Dip Switch
3. Capacity dip switch setting is below (dip switch should be set to the black

Summary of content (3 pages)