User Manual

Page 22mrcool.com
Unit Installation
WARNING
1. High and low voltage wires should be led through different rubber rings of the electric box
cover.
2. Do not bundle the thermostat wires or lay them side by side, otherwise errors will occur.
3. High and low voltage wires should be secured separately. Secure the former ones with large
clamps and the latter ones with small clamps.
4. Use screws to tighten the thermostat wires and power cords of the units on the terminal
board. Improper connection may create a fire hazard.
5. If the power cords and thermostat wires are not correctly connected, the air conditioner may
suffer damage.
6. Ground the units by connecting the ground wire.
7. The units should comply with applicable local and national rules and regulations on power
consumption.
8. When connecting the power cord, make sure the phase sequence of the power supply
matches with the corresponding terminals, otherwise the compressor will get reversed and
operate abnormally.
Electrical Connection
Connecting the Power Cord & Communication Wire
Electrical wiring of Single-phase unit: MDUI18024/MDUI18036
Fig. 2.13
Thermostat