Spec Sheet

Accessories
Kit Number Description Used with
MHK05B 5kW with Circuit Breaker 8, 12
MHK07B 7.5kW with Circuit Breaker 8, 12
MHK10B 10kW with Circuit Breaker All
MHK15B 15kW with Circuitl Breaker
20kW with Circuitl Breaker
12, 16, 20
*C - Constant or V - Variable
1 N = No circuit breaker
1 C = Circuit breaker
Electrical Data
Blower
Size
Electrical Heating Cap.
Blower
Amps
(2) (3) Total Amps per Circuit
Total Unit
Amps
MCA
Circuit Breaker
kW Btuh 208v 240v Amps per Stage
(1) 240v (1) 240v 208V 240V 1 2 3 1 2 3 208 240 208v 240v 1 2
08 (no heat) 0 0 2.6 2.4 --- --- --- --- --- --- 2.3 2.4 2.9 3.0 15 ---
08 5 17,100 2.6 2.4 20.7 --- --- 23.2 --- --- 20.7 23.2 25.8 29.0 30 ---
08 7.5 25,600 2.6 2.4 29.7 --- --- 33.7 --- --- 29.7 33.7 37.1 42.1 45 ---
08 10 34,100 2.6 2.4 38.7 --- --- 44.1 --- --- 37.7 44.1 48.4 55.1 60 ---
12 (no heat) 0 0 2.9 2.7 --- --- --- --- --- --- 2.9 2.7 3.6 3.4 15 ---
12 5 17,100 2.9 2.7 20.9 --- --- 23.5 --- --- 20.9 23.5 26.1 29.4 30 ---
12 7.5 25,600 2.9 2.7 30.0 --- --- 34.0 --- --- 30.0 34.0 37.5 42.5 45 ---
12 10 34,100 2.9 2.7 39.0 --- --- 44.4 --- --- 39.0 44.4 48.8 55.5 60 ---
12 15 51,200 2.9 2.7 39.0 18.1 --- 44.4 20.8 --- 57.1 65.2 71.4 81.5 60 30
16 (no heat) 0 0 3.8 3.5 --- --- --- --- --- --- 3.8 3.5 4.8 4.4 15 ---
16 10 34,100 3.8 3.5 39.9 --- --- 45.1 --- --- 39.9 45.1 49.9 56.4 60 ---
16 15 51,200 3.8 3.5 39.9 18.1 --- 45.1 20.8 --- 58.0 65.9 72.5 82.4 60 30
16 20 68,300 3.8 3.5 39.9 27.1 --- 45.1 41.7 --- 76.0 86.8 95.0 108.5 60 60
20 (no heat) 0 0 4.7 4.3 --- --- --- --- --- --- 0.0 0.0 0.0 0.0 15 ---
20 10 34,100 4.7 4.3 40.9 --- --- 45.9 --- --- 40.9 45.9 51.1 57.4 60 ---
20 15 51,200 4.7 4.3 40.9 18.1 --- 45.9 20.8 --- 59.0 66.7 73.8 83.4 60 30
20 20 68,300 4.7 4.3 40.9 36.1 --- 45.9 41.7 --- 77.0 87.6 96.3 109.5 60 60
If nominal CFM is 1000 (2.5 tons) with 15 kW electric heat, the motor speed must be set at medium or higher.
Maximum kW for units with nominal CFM set at 1400 (3.5 tons) is 15 kW.
For 208 volt use .751 correction factor for kW and Btuh.
15 and 20 kW (2 stage models) require 2 supply circuits.
Circuit #1 includes blower motor amps.
kW packages in bold indicate that these packages require and include circuite breakers. Optional for others.
NOTE:
ELECTRIC FURNACE MODULAR AIR SYSTEM MMBV*E
Page 3
mrcool.com