Install Manual

9
Table 6 Accessory Usage
ACCESSORY
REQUIRED FOR LOW---AMBIENT
COOLING APPLICATIONS
(Below 55F/12.8_C)
REQUIRED FOR LONG LINE
APPLICATIONS*
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
Ball Bearing Fan Motor Ye s{ No No
Compressor Start Assist Capacitor and Re lay Ye s Ye s No
Crankcase Heater Ye s Ye s No
Evaporator Freeze Thermostat Ye s No No
H a r d S h u t --- O f f T X V Ye s Ye s Ye s
Liquid Line Solenoid Valve No No No
Motor Master
or Low--- ambient Pressure Switch Ye s No No
Support Feet Recommended No Recommended
Winter Start Control Ye s No No
* For tubing l ine sets between 80 and 200 ft. ( 24.38 and 60.96 m) and/or 35 ft. ( 10.7 m) vertical differential, re f e r to Residential Piping and Longline Guideline.
{ Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FAN COIL
AIR
CONDITIONER
G
W2
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FURNACE
AIR
CONDITIONER
Y
G
W
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
A02326
LEGEND
24-V FACTORY WIRING
24-V FIELD WIRING
FIELD SPLICE CONNECTION
CONTACTOR
C
A97368
Fig. 8 -- Generic Wiring Diagrams
(See Thermostat Installation Instruction
for specific unit combinations)