PRODUCT NUMBER NOMENCLATURE PA14 N C 018 A B 00G 14 SEER Air Conditioner with Puron Refrigerant Series Variations Electrical Supply N – 208/230–60–1 00G – Variations C – Puron Nominal Capacity 018 – 1–1/2 Ton 024 – 2 Tons 030 – 2–1/2 Tons 036 – 3 Tons 042 – 3–1/2 Tons 048 – 4 Ton 060 – 5 Ton Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
REFRIGERANT PIPING LENGTH LIMITATIONS Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puronr Refrigerant: The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor units.
REFRIGERANT CHARGE ADJUSTMENTS Liquid Line Size Puron Charge oz/ft 3/8 0.60 (Factory charge for lineset = 9 oz) 5/16 0.40 1/4 0.27 Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above.
OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDOOR UNIT Check piston size shipped with indoor unit to see if it matches required indoor piston size. If it does not match, replace indoor piston with correct piston size in table below.
Accessory Description and Usage (Listed Alphabetically) 1. Ball--Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. Usage Guideline: Required on all units when MotorMasterr is used. 2. Compressor Start Assist -- Capacitor and Relay Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.
ELECTRICAL DATA UNIT SIZE --- SERIES V/PH OPER VOLTS* MAX COMPR MIN LRA 18--- A 47.5 24--- A 62.9 30--- A 67.8 36--- A 208/230/1 ---60 253 197 79.0 42--- A 109.0 48--- A 105.5 60--- A 127.1 * Permissible limits of the voltage range at which the unit will operate satisfactorily { Time ---Delay fuse. FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps NOTE: Control circuit is 24V on all units and requires external power source.
DIMENSIONS -- ENGLISH When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of unit and 12–in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.
DIMENSIONS -- SI When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of unit and 12–in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.
24” (609.6) Service 12” (304.8) Note: Numbers in ( ) = mm 18” (457.2) 24” (609.6) Service Wall 6” (152.4) 18” (457.2) 12” (304.8) 24” (609.6) Service Wall 18” (457.2) 12” (304.8) Clearances (various examples) 24” (609.6) Service 12” (304.8) 24” (609.6) Service Wall 6” (152.4) IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
TESTED AHRI COMBINATION RATINGS NOTE: Ratings contained in this document are subject to change at any time. For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org Additional ratings and system combinations can be accessed via the Payne database at: www.MyPayneRatings.
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) See notes on page 15 900 800 700 CFM EWB ° F (° C) EVAPORATOR AIR 675 600 525 CFM EWB ° F (° C) EVAPORATOR AIR 75 (23.9) 11.15 13.80 13.32 16.39 17.00 11.76 14.78 14.24 17.69 17.
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) See notes on page 15 1350 1200 1050 CFM EWB ° F (° C) EVAPORATOR AIR 1125 1000 875 CFM EWB ° F (° C) EVAPORATOR AIR 75 (23.9) 17.94 22.10 21.25 26.15 27.51 18.95 23.69 22.73 28.
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) See notes on page 15 1800 1600 1400 CFM EWB ° F (° C) EVAPORATOR AIR 1575 1400 1225 CFM EWB ° F (° C) EVAPORATOR AIR 75 (23.9) 25.57 31.68 30.38 37.63 38.17 27.01 33.98 32.51 39.
72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 72 (22.2) 67 (19.4) 63 (17.2)†† 62 (16.7) 57 (13.9) 68.41 62.24 57.78 56.92 55.64 69.54 63.30 58.79 58.25 57.80 70.37 64.08 59.56 59.69 59.58 35.82 44.04 42.37 52.17 55.64 37.55 46.83 44.95 55.83 57.80 39.17 49.47 47.41 59.69 59.58 Capacity MBtuh 75 (23.9) 4.01 4.01 4.02 4.02 4.02 4.10 4.11 4.11 4.11 4.11 4.20 4.20 4.20 4.20 4.20 Total System KW** 65.35 59.41 55.13 54.40 53.56 66.36 60.35 56.
CONDENSER ONLY RATINGS SST ° F (° C) 30 (-1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 30 (-1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 30 (-1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 30 (1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 55 (12.78) 65 (18.33) TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW 16.00 73.60 0.77 17.60 75.00 0.77 19.40 76.50 0.77 21.20 78.00 0.77 23.20 79.30 0.76 25.30 80.80 0.75 14.90 83.20 0.88 16.50 84.
CONDENSER ONLY RATINGS CONTINUED SST ° F (° C) 30 (-1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 30 (-1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 30 ( --- 1.11) 35 (1.67) 40 (4.44) 45 (7.22) 50 (10.0) 55 (12.78) 55 (12.78) 65 (18.33) TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW TCG SDT KW 33.60 67.80 1.73 37.10 69.00 1.73 40.80 70.20 1.74 44.90 71.60 1.74 49.30 73.00 1.75 54.00 74.50 1.75 32.00 77.30 1.92 35.30 78.50 1.93 38.90 79.70 1.94 42.70 80.90 1.94 46.90 82.
GUIDE SPECIFICATIONS GENERAL System Description Outdoor--mounted, air--cooled, split--system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air--cooled coil, propeller--type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.
SYSTEM DESIGN SUMMARY 1. 2. 3. 4. 5. 6. 7. 8. 9. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--IN W.C. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C). Maximum outdoor operating air temperature is 125_F (51.7_C). For reliable operation, unit should be level in all horizontal planes. For interconnecting refrigerant tube lengths greater than 80 ft (23.