DIMENSIONS -- SI SINGLE PHASE
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6βin. (152.4 mm) clearance on 1
side of unit and 12βin. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm)
between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m) Position so water, snow, or ice from roof or eaves
cannot fall directly on unit.
NOTE: 18β (457.2 mm) clearance option described above is approved for outdoor units with wire grille coil guard only. Units
with louver panels require 24β (609.6 mm) between units.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.