Specification

29
Dry Coil Air Delivery* -- Horizontal and Downflow Discharge Sizes 24--60 208/230VAC -- 1 Phase (Cont.)
Unit
Size
Heating Rise
Range
o
F(
o
C)
Motor
Speed
Wire
Color
External Static Pressure (IN. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
60130
35 --- 65
( 1 9 --- 3 6 )
Low
3
Blue
CFM 1330 1277 1232 1191 1147 1103 1060 1004 963 919
BHP 0.26 0.27 0.29 0.30 0.31 0.32 0.33 0.34 0.36 0.37
Heat Rise (
o
F) NA NA NA NA NA NA NA NA NA NA
Heat Rise (
o
C) NA NA NA NA NA NA NA NA NA NA
Med---Low Pink
CFM 1475 1436 1399 1351 1317 1270 1236 1188 1152 1105
BHP 0.35 0.36 0.37 0.38 0.40 0.41 0.42 0.43 0.45 0.45
Heat Rise (
o
F) 65 NA NA NA NA NA NA NA NA NA
Heat Rise (
o
C) 36 NA NA NA NA NA NA NA NA NA
Medium
2
Red
CFM 1736 1710 1668 1630 1600 1557 1522 1479 1450 1406
BHP 0.53 0.54 0.55 0.58 0.59 0.60 0.62 0.63 0.64 0.65
Heat Rise (
o
F) 55 56 57 59 60 62 63 65 NA NA
Heat Rise (
o
C) 31 31 32 33 33 34 35 36 NA NA
Med---High
1
Orange
CFM 1935 1909 1867 1836 1808 1766 1696 1619 1535 1454
BHP 0.71 0.73 0.74 0.76 0.78 0.79 0.77 0.75 0.72 0.68
Heat Rise (
o
F) 50 50 51 52 53 54 57 59 62 NA
Heat Rise (
o
C) 28 28 29 29 29 30 31 33 35 NA
High Black
CFM 2205 2150 2078 2011 1941 1852 1779 1672 1572 1473
BHP 1.04 1.02 0.99 0.95 0.92 0.87 0.85 0.79 0.75 0.70
Heat Rise (
o
F) 43 45 46 48 49 52 54 57 61 65
Heat Rise (
o
C) 24 25 26 26 27 29 30 32 34 36
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop table).
1
Factory-shipped heating speed
2
Factory-shipped cooling speed
3
Factory-shipped continuous fan speed
”NA = Not allowed for heatin g speed
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
PY4G -- -- B