Specification
34
Dry Coil Air Delivery* -- Horizontal Discharge Sizes 36 --60 3 Phase Models Only (Cont.)
Unit
Heating
Rise Range
Motor
Speed
Wire
Color
External Static Pressure (IN. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
60115
30 --- 60
o
F
(17 --- 33
o
C)
Low Blue
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating Rise (
o
F) 59 NA NA NA NA NA NA NA NA
Heating Rise (
o
C) 33 NA NA NA NA NA NA NA NA
Med---Low Pink
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating Rise (
o
F) 51 52 53 55 56 58 59 NA NA
Heating Rise (
o
C) 28 29 30 30 31 32 33 NA NA
Medium
2
Red
CFM 1962 1915 1880 1843 1794 1753 1711 1675 1628
Heating Rise (
o
F) 43 44 45 46 47 49 50 51 52
Heating Rise (
o
C) 24 25 25 26 26 27 28 28 29
M e d --- H i g h
1
Orange
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating Rise (
o
F) 40 41 41 42 43 44 45 46 48
Heating Rise (
o
C) 22 23 23 24 24 24 25 25 27
High Black
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating Rise (
o
F) 35 35 36 37 39 40 41 43 45
Heating Rise (
o
C) 19 20 20 21 22 22 23 24 25
60130
35 --- 65
o
F
(19 --- 36
o
C)
Low Blue
CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
Heating Rise (
o
F) NA NA NA NA NA NA NA NA NA
Heating Rise (
o
C) NA NA NA NA NA NA NA NA NA
Med---Low Pink
CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Heating Rise (
o
F) 57 58 59 61 63 65 NA NA NA
Heating Rise (
o
C) 32 32 33 34 35 36 NA NA NA
Medium
2
Red
CFM 1962 1915 1880 1843 1794 1753 1711 1675 1628
Heating Rise (
o
F) 49 50 51 52 53 54 56 57 58
Heating Rise (
o
C) 27 28 28 29 29 30 31 32 32
M e d --- H i g h
1
Orange
CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
Heating Rise (
o
F) 45 46 46 47 48 49 50 51 53
Heating Rise (
o
C) 25 25 26 26 27 27 28 28 30
High Black
CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
Heating Rise (
o
F) 39 40 41 42 43 44 46 48 51
Heating Rise (
o
C) 21 22 23 23 24 25 26 27 28
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop table).
1
Factory-shipped heating speed
2
Factory-shipped cooling speed
”NA” = Not allowed for heatin g speed
Note: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
PY4G -- -- B