SYJS-0308 Home MRV Service Manual 2003.
CONTENT 1. DESCRIPTION OF PRODUCTS & FEATURES 1.1 Nomenclature 1.2 Combination of indoor and outdoor 1.3 Models of indoor and outdoor units 1.4 Character of products 1.5 Cooling and heating capacity curves 2. SPECIFICATIONS 3. MECHANICAL DATA 3.1 Controllers/Instruction/Dimension 3.2 Refrigerant diagram 4. ELECTRICAL DATA 4.1 Wiring diagram 4.2 Circuit diagram 4.3 Resistance-Temperature character 5. NOISE LEVEL CHART 6. ELECTRICAL CONTROL FUNCTIONS 6.1 Indoor unit No. setting method 6.
1 DESCRIPTION OF PRODUCTS & FEATURES 1.
Equivalent power of outdoor unit Model of outdoor unit Total amount of indoor units can be connected with Types of indoor units can be connected with Capacity of indoor units can be connected with 3HP AU242FHAHA 3 sets 3 sets 3 sets AU242FHBHA 1 sets 2 sets See next page table Indoor units 9000~27000BTU/h 3. Models of indoor and outdoor units Outdoor units Appearance Model Refrigerant Capacity (BTU/h) Cooling AU422FIAHA Heating Connect capacity (HP) Min Single system R22 1.
indoor units type Four way cassette appearance refrigerant capacity(BTU/h) cooling heating AB092FCAHA R22 10000 12000 AB142FCAHA R22 14000 17000 AB092FCBHA R407C 9000 11000 AB142FCBHA R407C 14000 16000 AB182FCAHA R22 18000 21000 AB182FCBHA R407C 18000 21000 AC142FCBHA R407C 14000 16000 AC182FCBHA R407C 18000 21000 AC182FCAHA R22 18000 21000 AE072FCAKA R22 7000 9000 AE092FCAHA R22 9000 11000 AE092FCBHA R407C 9000 11000 AE182FCAHA R22 18000 21000 AE182F
AP182FAAHA R22 18000 21000 AP182FABHA R407C 18000 21000 AF092FCBHA R407C 9000 13000 AF122FCBHA R407C 12000 17000 AS062FMAHA R22 6000 8000 AS072FMAHA R22 7000 9000 AS092FMAHA R22 10000 13000 AS092FMBHA R407C 10000 13000 AS122FMAHA R22 12000 14000 AS122FBBHA R407C 12000 14000 AS182FTAHA R22 18000 21000 AS182FTBHA R407C 18000 21000 Cabinet Console Wall-mounted
4. Character of Products 1) The length of horizontal refrigerant pipe can reach 70m,the total pipe length can reach 100m, the height difference between indoors unit and outdoor unit can reach 30m, the height difference between indoor units can reach 10m. 2) 1000m super far distance communication between indoor and outdoor units, convenient control and easy to enlarge the scale of units assembly. 3) Indoor unit can be controlled separately.
5. Cooling and heating capacity curves (AU422FIAHA / AU422FIAIA / AU422FIBIA) 14.00 cooling capacity(kW) 13.50 13.00 12.50 12.00 11.50 11.00 10.50 10.00 18 23 28 33 38 43 heating capacity(kW) outdoor temp. 17.00 16.00 15.00 14.00 13.00 12.00 11.00 10.00 9.00 8.00 7.00 6.00 5.00 4.00 3.00 2.00 1.00 0.00 -15 -13 -11 -9 -7 -5 -3 -1 1 3 outdoor temp.
*** AU48- Characteristics of refrigerating and heating capacity 1) Calculation method 1.1 1.1 1.0 1.0 0.9 0.9 -5 0.
heating capacity( kW) (AU242FHAHA / AU242FHBHA) 11.00 10.00 9.00 8.00 7.00 6.00 5.00 4.00 3.00 2.00 1.00 0.00 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 outdoor temp. 10.00 cooling capacity(kW) 9.00 8.00 7.00 6.00 5.00 4.00 3.00 2.00 1.00 0.00 18 23 28 outdoor temp.
2 SPECIFICATIONS 1).
2).
3).
*** Item Function Capacity Total power input Max. power input Dehumidifying capacity Power source PIPING Outdoor unit Panel Indoor unit Running current(max. runnin current) Unit model (color) Fan Type × Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope External (L×W×H) Dimension Package (L×W×H) Drainage pipe (material , I.D./O.D.
*** Item Function Capacity Total power input Max. power input Dehumidifying capacity Power source Outdoor unit Panel Indoor unit Running current(max. runnin current) Unit model (color) Fan Type × Number Speed(H-M-L) Fan motor output power Air-flow(H-M-L) Heat exchanger Type / Diameter Total Area Temp. scope External (L×W×H) Dimension Package (L×W×H) Drainage pipe (material , I.D./O.D.
4).
AE072FCAKA 7000 Btu/h 9000 Btu/h W 1800 W 2400 10‐³×m³/h 1.2 Item Cooling capacity Heating capacity Cooling capacity Heating capacity Dehumidifying capacity model N,V,Hz 1PH 220V-230V 50HZ 1PH 220V-230V 50HZ Power source Refrigerant Noise level(H/M/L) R22 R22 dB(A) 36/-/centrifugal fan×2 36/-/centrifugal fan×2 m³/h 420 Relay control Combination of wave cranny radiation fin and copper pipe Capillary + Electronic expansion valve 663×440×225 11.6 6.35 9.
Item Cooling capacity Heating capacity Cooling capacity Heating capacity Dehumidifying capacity Power source Refrigerant Noise level(H/M/L) Fan model Btu/h Btu/h W W 10‐³×m³/h N,V,Hz dB(A) Type × Number Air-flow(H-M-L) starting mothod m³/h Heat exchanger Refrigerant control method Dimension(L×W×H) External Weight(unit/panel) Net Liquid Piping Gas Connection method Suited area mm×mm×mm kg / kg mm mm m2 Controller type Item Cooling capacity Heating capacity Cooling capacity Heating capacity Dehumidifyin
5).
6). Med static pressure duct type indoor unit Item Model AD142FCBHA AD182FCBHA Cooling capacity Btu/h 14000 18000 Heating capacity Btu/h 16000 21000 Power source 1PH 220-230V 50Hz 1PH 220-230V 50Hz Noise level H/M/L dB(A) 43/41/38 43/41/38 Dehumidifying capacity L/h 1.2 1.
8).
9). Ceiling concealed type TES indoor unit Item Model Cooling capacity Btu/h Heating capacity Btu/h Hot water capacity Btu/h Power source Pressure loss of hot water Kpa Water-flow L/h Inner cubage L Motor power W Noise level H/M/L dB(A) Dehumidifyng capacity L/h Refrigerant mm Dimension External L×W×H Package mm Weight Net/Gross Kg/Kg Type×Number Fan Power output(W) W Fan motor Starting method Air-flow m3/h Liquid mm Piping Gas mm Connecting method 10).
11). Wall-mounted type indoor unit Item Model AS092FMAHA AS092FMBHA Cooling capacity Btu/h 11000 9000 Heating capacity Btu/h 14000 10000 Power source 1PH 220-230V 50Hz 1PH 220-230V 50Hz Noise level H/M/L dB(A) 39/37/30 39/37/30 Dehumidifying capacity L/h 1.6 1.6 Refrigerant R22 R407C External mm 795×182×265 795×182×265 Dimension L×W×H Package mm 860×335×270 860×335×270 Net Kg 7.6 7.6 Weight Gross Kg 10.6 10.
AS072FMAHA Btu/h 7000 Btu/h 9000 2500 W 3000 W 10‐³×m³/h 1.
3 MECHANICAL DATA 3.1 Controllers 3.1.1 Wireless remote controller Signal Transmitter Mode Sending signals to the indoor unit receiver Operation option display Airflow volume AUTO Airflow volume display Speed is automatically adjusted by the air conditioner according to room and set temperatures.
*** Remote controller 1.POWER ON/OFF used for unit start and stop Buttons and display of the remote controller 2.TEMPERATURE 20 11 12 15 AUTO 16 ion 13 17 18 OFF 14 3 . H E A LT H used to control the function of oxygenmaking and ion-adding (when oxygen device and ion-generator are both acquirable*health button can control them, whether oxygen device is acquirable lies on the function of its outdoor.) 4.MODE H 19 TEMP 2 ON HEALTH 4 used to select your desired temp.
3.1.2 Wired remote controller (old type) Heating operation indication Dehumidifying operation indication Cooling operation indication Fan only operation indication Automatic operation Operation indicator Clock display Power ON/OFF key Used to turn on /off the machine.
3.1.3 Wired remote controller (new type) MODE CLOCK Used to select AUTO RUN, COOL, DRY, HEAT and FAN operation. Used to set correct time. TIMER Used to select TIMER ON, TIMER OFF, TIMER ON/OFF. Dial switch and Sensor FAN SPEED MODE FAN SWING Used to select fan speed: LO, MED, HI, AUTO AUTO TEMP SET % ON AM PM CLOCK SET TIMER SLEEP * ROOM Used to set clock and timer setting. Power ON/OFF Used for unit start and stop. Used to select your desired temp.
DRY HEAT FAN OPERATION COOL SLEEP AUTO MODE FAN SWING AUTO TEMP SET % ROOM ON AM PM CLOCK SET TIMER SLEEP • FILTER RESET RESET OFF AM PM ON/OFF FAN SPEED TIMER ON TIMER OFF CLOCK OPERATING LAMP Remote control TEMP. Clock set When unit is started for the first time, clock should be adjusted as follows: Press CLOCK button, "AM"or "PM" flashes. Press or to set correct time. Each press will increase or decrease 1min. If the button is kept depressed, time will change quickly.
3.2 Refrigerant Diagram 3.2.
Model AU242FHAHA / AU242FHBHA 4-way valve Electromagnetic valve Capillary Oil separator 3-way stop valve Discharging gas temperature Pressure switch sensor Compressor Refrigerant storage Filter device 2-way stop valve Electronic expansion valve Capillary Suction gas temperature sensor Gas &liquid separator Outdoor heat exchanger Defrosting Evaporating sensor sensor
***MODEL AU482FIAHA AU48NFIAHA
3.2.2 Cooling system of indoor unit (take single system connected with 3 sets of AS092FMAHA as an example) Electronic expansion valve Liquid pipe sensor Indoor heat exchanger Gas pipe sensor 3.2.3 The function of all kinds of heat sensitive resisters and pressure switch (1) Outdoor unit A.
motor together with outdoor ambient temperature heat sensitive resister; when heating, as the condition to enter and quit from defrosting. D. Pressure switch: used to prevent the air discharging pressure of compressor from too high. (2) Indoor unit A. Indoors ambient temperature heat sensitive resister: together with temperature set as the ground to control thermostat. B.
4 ELECTRICAL DATA 4.1 Wiring Diagram 4.1.
2) Model: AU422FIAIA / AU422FIBIA
3) model: AU242FHAHA / AU242FHBHA
***AU482FIAHA CN21 red CN22 CN19 power module SW06 LD1 LD2 LD3 white black CN20 SW07 compressor filter capacitor SW05 SW04 SW01 SW02 Weak-electric Control Board SW RL3 RL2 Strong-electric Control Board fuse black RL4 RL6 RL1 capacitor RL5 capacitor P red red red orange white grey blue yellow red black black white red white grey yellow orange black red condenser mid-part sensor electronic electronic expansion valve 2 expansion valve 1 suction sensor discharging defrosting sens
***AU48NFIAHA white black red power module compressor filter capacitor condenser mid-part sensor SW06 LD1 LD2 LD3 suction sensor SW07 SW05 SW04 ambient temp.
4.1.
2) Model: AS182FTAHA / AS182FTBHA 3) Model: AP182FAAHA Vapor pipe temperature sensor Control board Ambient temperature sensor Liquid pipe temperature sensor Terminal block Connect with outdoor unit Electronic expansion valve Negative ion generator Note: It is strictly prohibited to connect C1, C2 with 220V power Fan motor Fan motor capacitor Louver motor Color instruction: B : Black R: Red G: Green BL: Blue W: White Y/G: Yellow/Green OR: Orange Y: Yellow
4) Model: AB092FCBHA / AB142FCBHA / AB182FCAHA ELECTRO-EXPANSION VALVE M CN6 CN5 W 串行口 250VAC,3.15A GAS PIPING TEMP.SENSOR INDOOR PCB TEST CN16 CN17 CN18 B ROOM TEMP.SENSOR CN4 LIQUID PIPING TEMP.SENSOR FLOAT SWITCH BL B CN15 CN14 CN13 CN12 CN10 CN11 CN1 COM LO MED HI SIGNAL RECEIVER BOARD R R W B W B Y/G R Y Y Y/G R W M C1 C2 N L M M PUMP LOUVER MOTOR CAPACITOR FAN MOTOR TO OUTDOOR UNIT 5) Model: AC142FCBHA / AC182FCBHA / AC182FCAHA W GAS PIPING TEMP.
6) Model: AE092FCAHA /AE092FCBHA /AE182FCAHA /AE182FCBHA M CN6 ELECTRO-EXPANSION VALVE INDOOR PCB CN5 GAS PIPE LIQUID PIPE UNIT NUMBER SERTING CN2 WIRING REMOTE CONTROLLER CN14 CN1 CN13 CN10 250VAC,3.
8) Model: AF092FCBHA / AF122FCBHA 9) Model: AD142FCBHA / AD182FCBHA 0010570373
MP3 wiring diagram: Electronic expansion valve wiring diagram FUSE T3.
AE072FCAKA、AE092FCAKA、AE122FCAKA、AE182FCAKA、AE212FCAKA、AE242FCAKA: Indoor unit wiring diagram M electronic expansion valve M refresh air fan motor blue 1 1 2 3 4 5 6 CN6 1 2 3 CN9 CN17 CN5 1 2 3 4 blue 2 3 CN8 black gas pipe temp. sensor liquid pipe temp. sensor NOTE:the dashed "---"in indoor controll board is PCB inner wiring. About control board outer connector: in the diagram,gas pipe temp. sensor 、liquid pipe temp.
4.2 Circuit Diagram 4.2.
Model: expansion valve MRV circuit diagram of control board for electrical expansion valve
Model: AS182FTAHA / AS182FTBHA
Model: AB182FCAHA /AB182FCBHA / AB092FCBHA / AB142FCBHA
Model: AC182FCAHA / AC182FCBHA / AC142FCBHA
Model: AD142FCBHIA / AD182FCBHIA
Model: AE092FCAHA / AE092FCBHA / AE182FCAHA / AE182FCBHA
MP3 circuit diagram:
Model: AP182FAAHA
Model: AE112FCBIA / AE182FCBIA (TES)
Model: AF092FCBHA / AF122FCBHA
Model: AP182FAAHA / AP182FABHA
4.2.
Power PCB schematic
AU24FAAHA/AU242FHBHA Control PCB schematic Power PCB schematic
4.3 Resistance-Temperature character Value of the heat sensitive resistance of defrosting, suction air, outdoor ambient temperature, evaporator, gas pipe and liquid pipe. Temperature ( ) Resistance value (k ) Temperature ( ) Resistance value (k -10 53.0 40 5.5 -5 41.2 45 4.6 0 31.9 50 3.8 5 23.9 55 3.2 10 18.9 60 2.7 15 15.5 65 2.3 20 12.3 70 1.9 25 9.9 75 1.7 30 8.1 80 1.4 35 6.6 85 1.
6 ELECTRICAL CONTROL FUNCTIONS 6.1 Indoor unit NO. Setting method 6.1.1 In order to control all indoor units of H-MRV systems, the indoor units number should be set after installation work. We have two ways to set indoor unit number according to indoor unit type. Normally the infrared remote control types use special remote controller to do indoor unit number setting, the wired types use dialing switch (on indoor unit PCB) to do indoor unit number setting. The details is as follows : No.
6.1.2 Function of special remote controller (Adress setting) 1. Read function symbol Press “read” button , “1” flashes 1 time 2 2. Signal emitting symbol when “2” flashes ,it shows that remote controller is giving signal to indoor unit. press “8”button to select indoor unit number (1,2,3,4,5or6), then “3” flashes continuously ,press “7” to set indoor unit number 4. Button locked symbol When “9” is on the state of “ ↗”,press “10”button , “4” appears to show other buttons are locked .
6.1.3 Number setting dialing switch using method(wired remoted control type) The dialing switch is on indoor unit PCB. The indoor unit number setting method is as follows: OFF stand for NO.1 indoor unit Digit 1 0 1 0 1 0 1 Digit 2 0 0 1 1 0 0 Digit 3 0 0 0 0 1 1 stand for NO.2 indoor unit Digit 4 Not used Not used Not used Not used Not used Not used Unit number stand for 1 2 3 4 5 6 7.1.4 Indoor unit NO. lock switch (for model AU422FIAHA,AU422FIAIA, AU422F I B H A) We have “indoor unit NO.
6.
(2) Turn on/off unit Control function treat module Off Power indicator turn off, operation indicator turn off On/off On Yes Trouble signal Trouble indication Off Mode determinatio Yes Abnormal operation n Buzzer sound twice, refuse to receive signal No Choose mode Cooling operation Heating operation Dehumidifying operation A Fan motor turn off, electronic expansion valve close, louver motor turn off
(3) Cooling operation Cooling operation No Swing flap in the cooling standard position Swing Yes Swing action Yes Automatic fan speed Adjust fan speed according to temperature set and in air temperature No Operate in speed set fan Electronic expansion valve: overheat control Swing flap: cooling standard position Fan motor: high speed Yes Test run No Yes Electronic expansion valve: overheat control. Swing flap: cooling standard position.
(4) Dehumidifying operation Dehumidifying operation No Swing flap in the cooling standard position Swing Yes Swing action Yes If enter cooling operation Adjust fan speed according to temperature set and in air temperature No No Determine if dehumidify according to in air temperature Yes Electronic expansion valves open, indoor unit fan motor weak wind Electronic expansion valves open, indoor unit fan motor weak wind Yes Electronic expansion valve totally open Antidefrosting No Send indoor Operat
(5) Heating operation Heating operation No Swing flap in set fan speed position Swing Yes Swing action Yes Defrosting On side: wind off, expansion valve steady Off side: Electronic expansion valve totally open No No Rated operation According to temperature sensor to adjust state and valve open degree Fan motor operate in rated fan speed Yes If stop unit protection Overload protection No Yes No (not rated operation) Electronic expansion valve close Auto fan speed Yes Operate in set fan spe
6.3 Defrost operation Flow Chart 1. The compressor operates heating over 25 minutes, after meeting the defrosting condition, it is permitted to enter defrosting. Defrosting process is unit-stop defrosting mode. Determining condition of defrosting is as follows: Unit-stop defrosting: (1) When outdoor ambient temperature is less than 2 , (outdoor ambient temperaturedefrosting sensor) is more than 9 , and keeping over 2 minutes, enter unit-stop defrosting.
2. Compressor control The compressor will start at 10Hz and running between 30Hz to 120Hz. In operation the compressor running frequency is determined by three elements : the number of indoor units in operation , the temperature difference of each indoor units between setting temperature and room temperature , the size of each indoor unit. 3.
7 DIAGNOSTIC INFORMATION (TROUBLE SHOOTING) 7.1 Fault Codes In order to make repair and maintenance convenient, we set “Automatic troubleshooting” function in indoor unit and centralized controller. If any abnormal phenomenon occurs in operation, you can determine the trouble part and condition from the indicator light in indoor unit or the trouble code on the centralized controller.
Indoor unit malfunction display code Indoor unit malfunction Float switch or water motor abnormal Outdoor unit abnormal Setting running mode is different with outdoor running mode Liquid temperature sensor is abnormal Gas temperature sensor is abnormal The communication between indoor 846 chip and communication chip is abnormal The communication with electronic expansion box is abnormal The communication between the wire remote controller and indoor unit control board is abnormal The communication between i
10.2 AU48- diagnostic information and trouble shooting The failure code is displayed on the outdoor PCB; please diagnose the trouble according to the following code: Failure code Failure position Judgment measure 01 Outdoor defrosting sensor TE circuit 02 Ambient circuit temp. sensor TA Examine the sensor below 20H in cut circuit or over 1000H in short circuit for continuous 60 seconds, recoverable 03 Suction circuit temp.
minutes normally 14 Low pressure protection acts Cooling: examine Ps below 0.2kgG/cm2 for 30 (Ps) seconds continuously after compressor starts up; Heating: examine Ps below -0.2kgG/cm2 for 10 minutes continuously after compressor starts up; recoverable 15 High pressure protection acts (Pd) Examine sensor Pd over 27.5kgG/cm2 16 Suction temp. protection acts (TS) On compressor working, for continuous 10 minutes, examine sensor TS over 40℃, recover after 2 minutes.
7.2 Troubleshooting (1) Indoor unit trouble indication: timer indicator flashes (once, twice, 3 times, 7 times) Abnormal reasons: Heat sensitive resister is short circuit or open circuit The treatment to sensor output part in PC board is improper, such as poor contact of package part, the electrolytic capacitor for filtering is failed, etc. Treatment: Remove the heat sensitive resister, test and measure its numerical value.
Treatment: use the DC voltage grade of multimeter to test the plastic sealed motor to find if there is any feedback signal, determine if the plastic sealed motor is abnormal. If normal, change the indoor unit PC board. (6) Indoor unit trouble indication: Timer indicator flashes (12 times) Abnormal reason: Indoor unit PC board is improper Treatment: change the improper indoor unit PC board.
Refrigerant leaks Discharging air temperature heat sensitive resistor is improper Electronic expansion valve or 2-way valve is closed Treatment: check if there is leakage part, test system pressure in rated operation state to determine if there is leakage? Check the state of electronic expansion valve and 2-way valve. Test and measure the numerical value of discharging air temperature heat sensitive resister. 7.3 Example of repair (1) Phenomenon: after changing the PC board of outdoor unit, do not reset.
8 INSTALLATION 8.1 Piping dimensions chart Liquid pipe Model mm 9.52 9.52 6.35 6.35 9.52 9.52 9.52 9.52 9.52 6.35 6.35 9.52 9.52 6.35 6.35 9.52 6.35 9.52 AU42 AU24 AB09 AB14 AB18 AC14 AC18 AD14 AD18 AE09 AE11 (TES) AE18 AE18 (TES) AF09 AF12 AP18 AS09 AS18 Gas pipe inch 3/8” 3/8” 1/4” 1/4” 3/8” 3/8” 3/8” 3/8” 3/8” 1/4” 1/4” 3/8” 3/8” 1/4” 1/4” 3/8” 1/4” 3/8” mm 15.88 15.88 9.52 12.7 15.88 15.88 15.88 15.88 15.88 9.52 12.7 15.88 15.88 12.7 12.7 15.88 12.7 15.
FQG-B180 gas pipe heat preservation material liquid pipe heat preservation material Refrigerant pipes between manifold pipes Total refrigerating amount of indoor unit Gas side Liquid side group after the manifold pipe Less than 38220Btu/h 15.9 9.52 38220~61157Btu/h 19.05 9.52 61157~126137Btu/h 25.4 12.7 Note: 1. Y-shape manifold pipe can be placed in horizontal or vertical direction 2. The manifold pipes must be welded with hard-solder 3.
In the file, the figure marked with "√" is permitted, and the figure marked with "×" is prohibited. You can confirm the position according to the actual condition. The refrigerant flow direction is always from the collective side to the divided side.
8.3 Piping length and drop between units (AU48-) Haier MP2 H 1) When connected with 8 units,indoor units refer to 2) Total length=l1+l2*2+l3*4+l4*4+l5*4<=100m 3) Max. piping length =(l1+l2+l3+l5)<=70m 4) Max. piping length between the indoor unit and the first branch pipe<=30m 5) Max. drop between outdoor unit and indoor unit: H<=30m(indoor above outdoor);H<=20m(indoor below outdoor) 6) Max.
Combination example:(AU48-) 8 by 1: AS06 Haier AS06 electronic expansion valve AS06 AS06 AS06 AS06 AE07 MP2 AE07 NOTE: 1.When AU48 unit is connected with 8 indoor units, pay attention that the total capacity of indoor units must not exceed 130% of outdoor cooling capacity. 2.Wall-mounted type can not be connected with 8 units by the outdoor unit. But you can refer to the above combination example. 3.
8.3 Piping i length and drop between the units l4 Haier AP18 l2 l3 d AU42- AU48- AS09 Expansion valve l6 H<=30m l1 d l5 d AS09 h<=10 m AS09 AS09 Haier AS09 l1 l2 l3 h<=10 m AS09 1) Total length=l1+l2+l3+l4+l5+l6+2*d<=100m 2) Max. piping length of single system=(l1+l2+l3)or( l4)<=50m 3) d<=15m 4) Max. drop between outdoor unit and indoor unit: H<=30m 5) Max. drop between the two units in the same system: h<=10m 6) Max.
8.4 Combination examples A. 6 by one AS09 (or other 9000BTU units) AS09 (or other 9000BTU units) Haier AS09 (or other 9000BTU units) A B AU42- AU48- AS09 (or other 9000BTU units) AS09 (or other 9000BTU units) Expansion valve AS09 (or other 9000BTU units) B.
C. 4 by one AP18(or other 18000BTU,14000BTU units) Haier A AU42- AU48- AB09(or other 9000BTU,12000BTU units) B AS09(or other 9000BTU,12000BTU units) AC18(or other 18000BTU,14000BTU units) D.
E. 3 by one AS09( or other 9000 BTU units) Haier AS09( or other 9000 BTU units) AS09( or other 9000 BTU units) F.
8.5 Installation dimensions A. model: AU42- ***AU48- 190 580 190 340 380 30 52 Screw Hole (M10) 88 960 25 1250 Power wiring Terminal Back Air-flow Hole L2 L3 L4 Installation Servicing Space(at Least) Unit:mm Back Airflow Hole L1 Outlet Air-flow Hole Repairing Space Installation Dimension Note : (1). Fix the parts with screws (2).Don't intake the strong wind directly to the outlet air-flow hole. (3).A one meter distance should be kept from the unit top (4).
B. model: AU24- 190 190 580 340 380 55 Screw Hole (M10) 70 1024 70 Power Wiring Terminal 25 840 Power Wiring Distribution Hole Back Air-flow Hole L2 L3 Installation Servicing Space(at Least) L4 Unit:mm Back Airflow Hole L1 Outlet Air-flow Hole Repairing Space Installation Dimension Note (1) Fix the parts with screws (2)Don't intake the strong wind directly to the outlet air-flow hole.
Model: AB092FCAHA AB142FCAHA 2 40 30 75 362 18 122 5 104 35 660 48 660 270 170 32 131 113 90 70 30 270 45 92 Model: AB182FCAHA
Model: AC182FCAHA 0 0 2 9 Model: Wall mounted Aa Ac Ab AS062FMAHA AS072FMAHA AS092FMAHA AS122FMAHA AS122FBBHA AS182FTAHA AS182FTBHA a 795 795 795 938 938 1100 1100 b 182 182 182 182 182 205 205 c 265 265 265 265 265 300 300 240 5 5 6
Model: ceiling concealed 54 25 100 25 225 b a 0 R1 225 55 122 240 C 30 R5 OVER 250 93 a b c 615 702 452 AE122FCAKA 770 704 452 AE142FCAKA 770 704 452 AB182FCAKA 990 858 452 AE212FCAKA 990 858 452 unit model AE092FCAKA AE242FCAKA
Model: AP182FAAHA 250 500 1746 5
8.
l l l l l l l l l l l work is not met with the requirements, overturn of the unit will occur resulting in accidents. The wiring work shall be done by a qualified person and referred to the “technical standard of electric equipment”, “indoor wiring regulation” and what the manual specified. Do use special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other accidents will happen.
8.8 Special Work and Main Points in Installation Warning l l During installation, if refrigerant l leakage occurs, take ventilation measurement immediately. l As soon as the leaked refrigerant gas meets fire, poisonous gas will generate. After finishing installation, confirm the refrigerant gas does not leak. If the refrigerant gas leaks in the room, once it meets heater, burner and gas stove etc. fire source, the poisonous gas will generate. A.
(4) Pipe connection of the outdoor unit Referring to the installation diagram in page 4, connect the indoor unit, outdoor unit, branch pipe and electronic expansion valve together by using the pipe connection method and welding method. (5) Test of airtight quality After connection of the refrigerant pipes, carry out airtight quality test.
8.9 Test of leakage after wiring work is finished After connection of the refrigerant pipes, carry out leakage test. In this test, pressurize to the pipes as shown in the below figure by using nitrogen tank. Close the valves of the gas side and liquid side totally. The nitrogen may enter the cycle system of the outdoor unit, so that, before pressurizing, the valve rods must be fastened. (Both the gas side and liquid side).
c. Vacuumize 2~3 hours according to the length of the pipe. When vacuuming, confirm the gas side and liquid side of the 2-way valve and 3-way valve shall be in full close state. d. When it is not lower than 200Pa after 2 hours or more vacuuming, vacuums for another 1 hour. If after more than 3 hours vacuuming it is still not lower than 200Pa, the leak part shall be found. e.
8.11 Refrigerant MRV central air conditioner uses refrigerant “R22”. This refrigerant itself is innocuous, non-combustible safety refrigerant. But then, when arranging the air conditioner equipment, it is necessary to take some steps to take precautions against in case of the indoors refrigerant leakage. Such as, the room size shall be taken into account to avoid making the concentration of the refrigerant not exceed the concentration limit and other relevant steps.
8.12 Electric wiring Note: l l l l l l l The air conditioner must use special circuit (over 40A), and wiring by the qualified electrician according to the wiring rules specified in national standard. The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is incorrect. The electric leakage breaker must be installed. All the electric wire must be copper wire.
Wiring method 1. Wiring method of orbicular terminals For the connection wire with orbicular terminals, its wiring method is as shown in the right figure: remove the connecting screw, put the screw through the ring on the end of the wire, then connect to the terminal block and fasten screw. 2.
2. Do not connect the power line with different dimensions to the same grounding wire end. Improper contact will affect protection. 3. Keep a proper distance between the communication wire and the power line. Otherwise, abnormal communication will occur because of disturbance. 4. Do not connect the power line to the connecting end of communication wire. Incorrect connection will cause damage of connected unit. 5.The communication wire must be shielding wire. Wiring example diagram: 8.
a. Unit number setting of outdoor unit (now it is unuseful) Unit number setting switch of outdoor unit and confirming of setting. 4-digit number setting dialing switch and corresponding nixie tube confirming display are equipped on the outdoor unit. Setting mode as follows: Before electrifying, manually set the outdoor unit number according the following table. After electrifying, the nixie tube displays letter “P”.
l l l l l l appear. When using special remote controller to do unit number setting, it shall be done at a place 1m away from the infrared receiver window. The specific setting method as follows: press the number button according to the unit number to be set, then press set button to send signal.
8.14 Checks after the installation After installation, please fill in the following form for easy daily maintenance: No. Model of indoor unit Factory No. of unit Site setting No. System belonged (A/B) 1 2 3 4 5 6 Check for installation and test run z z z z z z z z z z z Please operate the air conditioner according to the operation manual.
more than 5.2 Installation of indoor unit for console type mo re Installation of indoor unit selection of installation place tha n mo re tha n han re t mo Fig1 617 330 Fig2 Fig3 Tool necessary 1. Screw driver 2. Hacksaw 3. 70mm dia.hole core drill 4. Spanner(dia. 17,27mm) 5. Spanner(14,17,27mm) 6. Pipe cutter 7. Flaring tool 8. Knife 9. Nipper 10. Gas leakage detector or soap water 11. Measuring tape 12. Reamer 13.
Fixing of the unit Indoor side 1.Position of the wall hole Wall hole should be decided according to installation Wall hole place and piping direction.(refer to installation drawings). 70mm Outdoor side Thickness of wall 2. Making a wall hole Drill a hole of 120X70mm dia. with a little slope towards outside. (Cross section of wall hole) 3.
Piping connection of the indoor unit 1. Arrangement of piping and drainage pipe After opening inlet grill,you will see a control box. Remove the cover before working. Cut away, with a hammer or a saw, the lid for piping according to piping direction. Insulation material Drain hose Copper tube Connecting electric cable for indoor and outdoor unit According to the piping method, connect the piping on indoor unit with union of connection pipe.
Wiring diagram: Block terminals for indoor unit N L C1 C2 W B Y/G R R NOTE: W:WHITE Block terminals N L for outdoor unit W B Y/G (different outdoor unit have different block terminals) B:BLACK C1 C2 Y/G:YELLOW/GREEN R R:RED R Note: When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal blocks. Terminals of same number and same color shall be connected by the same wire. Incorrect wiring may damage air conditioner's control or cause operation failure. Others 1.
5.3 Installation Instructions of wall mounted type Installation Tools 1) Screw Driver 2) Hacksaw 3) Hole core drill 4) Hexagon wrench (5mm) 5) Spanner (14,17,19 and 24mm) 6) Torque wrench (17,22,24mm) 7) Pipe cutter 8) Flaring tool Standard Accessories The standard accessories includes: 1) Measuring type 2) Reamer 3) Refrigerant oil 4) Gas leakage detector or soap-and-water solution 5) Knife 6) Nipper NO.
NO.
The installation of wall mounted type Indoor Unit 1 Fitting of the Mounting plate and Positioning of the Wall Hole When the mounting plate is first fixed 1 Carry out,based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall,then temporarily fasten the plate with one steel nail. 2 Make sure once more the proper level of the plate,by hanging a thread with a weight from the central top of the plate,then fasten securely the plate with the attachment steel nail.
3 lnstallation of the lndoor Unit Drawing of pipe [Rear piping] Draw pipes and the drain hose, then fasten them and connecting electric cable for indoor and outdoor with the adhesive tape. Drain hose should be placed under.
5.4 Installation of ceiling concealed type Installation of indoor unit When installing the ceiling concealed type indoor unit, a specially designed return air bellows shall be installed, as shown in Figure 3, Figure 4. Figure 3 Installing building roof *0.
Indoor unit flexible joint or static pressure box transitive air duct circular air duct joint of air diffuser air diffuser Fig1: Duct connected 2. Installation for air return duct Use rivets to connect the air return duct to the air return inlet of the indoor unit. The other end connects to the air return shutter. as shown in Fig.2. air return shutter air return duct indoor unit rivet Fig2: Duct return connected 3. Air duct insulation Insulation layer is needed for air supply and return duct.
Iron reinforcement Foundation bolt Knife embedded part Guide plate embedded part Pipe suspension foundation bolt Original concrete slab Use hole hinge, hole plunger or hole bolt. Steel reinforcement structure Use steel angle or new support steel angle directly. Hanging bolt Suspension screw Support steel angle Hanging of the indoor unit l l Fasten the nut on the suspension screw and then hang the suspension screw in the T slot of the suspension part of the unit.
Installation of remote controller Upper cover of wire controller 1. Remove upper cover of wire controller Remove upper part of wire controller by press. Lower cover of wire controller PCB is mounted on lower part of wire controller, be careful not to damage it. 2.
Drain pipe ! Caution In order to drain water normally, the drain pipe shall be processed as specified in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage. Requirements The indoor drain pipe shall be thermal insulated. The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation. The drain pipe shall be slant downwards (greater than 1/100).
Installation Procedure Refrigerant piping Allowable pipe length and drop These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details. Pipe material and size Pipe material Phosphorus deoxidized copper seamless pipe (TP2M) for air conditioner Model Pipe size (mm) AE072- AE092- AE122- Gas side 12.7 12.7 12.7 Liquid side 6.35 6.35 6.
Installation Procedure Refrigerant piping Vacuum pumping With a vacuum pump, create vacuum from the stop valve of the outdoor unit. l Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden. Open all valves Open all the valves on the outdoor unit. Gas leakage detection Check with a leakage detector or soap water that if there is gas leakage at the pipe connections and bonnets.
Installation Procedure ! Warning Electric wiring ! The electric wiring work shall be conducted by qualified electricians according to the installation instructions. A separate power circuit shall be used. Insufficient power cord amperage or improper wiring will cause danger of electric shock or fire. During wiring connection, the power cord shall be of the specified cable and reliably fastened so that external forces applied to the cable wouldnt transfer to the terminals.
Wire connection for built-in indoor unit Insert from outside the connection wire and signal transmission wire through the wall hole with pipeline already arranged. Pull out the front ends of connection wire and signal wire and make a circle on the signal wire. Connect the connection wire according to the connection method and indoor and outdoor wiring diagram. Pull the connecting conductor outwards slightly to confirm it is clamped tightly.
5.
INSTALLATION INSTRUCTIONS 5 INSTALLATION INSTRUCTIONS (For cassette type) 5.1 Installation tools 1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner, shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter 7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor 11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump 15 .Flat screwdriver 5.
INSTALLATION INSTRUCTIONS Air outlet 1500 Over 2500 Over Air inlet 260 260 (2) Ceiling height Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to 8 Foeld setting and Installation Manual of ornament panel.) (3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern.
INSTALLATION INSTRUCTIONS (2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer 50~100 (3) Install a suspending bolt.
INSTALLATION INSTRUCTIONS 5.3.4 Installation In the case of new ceiling (1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. (2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern 4 onto unit using 3 screws 5 .
INSTALLATION INSTRUCTIONS 5.3.6 Installation of drainage pipe (1) Install water drainage pipe Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm) Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening. If downward slope can't be made, take other measures to lift it up. Keep a distance of 1-1.5m between suspending brackets, to make water hose straight. 1-1.
9 EXPLODED VIEWS & PART LISTS 9.
AU422FIAHA No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 AU422FIAIA 30 / AU422FIAIA Specialized Number 001A0100122 001A0100493 001A1301640 001A5402022 001A3000201 001A0100826 001A17421215 001A1301469 001A0400132 001A17341206 001A3800138 001A2500094 001A5736055 001A0100827 001A0100495 001A0100494 001A1436160 001A1301465 001A3800105 001A2500087 001A2500095 001A2000128 001A2500098 001A2500099 001A2500100 001A2500101 001A1301685 001A0100497 001A13011200.
AU422FIBIA No.
Model: AU482FIAIA / AU48NFIAIA
Parts list No.
Parts list Spare parts No. number Spare parts description in English the proportion of the sparepart stock Remark Qty. Model Failure rate 1 2 3 4 5 001A0100122 001A1301707 001A1301640 001A5402022 001A3000201 Front guard assy Plate for maintain Front panel(left) Axial Fan Motor 2 1 1 2 2 AU48NFIAIA AU48NFIAIA AU48NFIAIA AU48NFIAIA AU48NFIAIA 0.00% 0.00% 0.00% 0.02% 0.02% 0.000% 0.000% 0.000% 0.024% 0.
AU422FIAHA / AU422FIAIA / AU422FIBIA Electrical system
AU422FIAHA / AU422FIAIA No.
Parts list Spare parts No. number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 0010150073 0010450036 0010450184 / 001A5745116 0010450037 0010450187 0010450188 0010450201 0010450200 / 0010450189 0010450190 001A3600018 0010150075 Spare parts description in English Electrical box PCB 1 power supply Terminal board / Terminal board PCB 2 rectifier rectifier power module dispel heat patch / electrolyse capacitance 1 electrolyse capacitance 2 Capacitor for fan motor Electrical box(level) Qty.
Model: AU242FHAHA / AU242FHBHA
Parts list the proportion of Spare parts Spare parts description in Failure the spare-part No. number English Qty. Model rate stock Remark 1 001A5002108 Screw 2 AU242FHAHA 0.0000% 0.0000% X 2 001A0100122 Front guard assy 1 AU242FHAHA 0.0000% 0.0000% X 3 001A1436160 Handle 2 AU242FHAHA 0.0000% 0.0000% X 4 001A1101078 Front Panel 1 AU242FHAHA 0.0000% 0.0000% X 5 001A5102027 Nut 1 AU242FHAHA 0.0000% 0.0000% X 6 001A5402022 Axial fan 1 AU242FHAHA 0.0200% 0.
Parts list No.
MODEL : AB092FCBHA / AB142FCBHA /AB182FCBHA
AB092FCBHA / AB142FCBHA NO. Name of part Specialized Number QTY NO. Name of part Specialized Number QTY 1 Guard assembly 0010800868 1 28 Swing motor assembly 0010850097 1 2 Indoor fan motor 0010400705 1 29 Holding pole 0010250056 2 3 Motor fix plate 0010100531 1 30 Connecting rod 0010250062 3 4 Swing 001A13011049 4 31 Coupler 0010250063 6 5 Ventilate duct 0010800873 1 32 Connection 0010250064 8 6 Centrifugal fan 0010250024 1 33 Ambient temp.
AB182FCBHA NO. Name of part Specialized Number QTY NO. Name of part Specialized Number QTY 1 Guard assembly 0010800868 1 28 Swing motor assembly 0010850097 1 2 Indoor fan motor 0010400705 1 29 Holding pole 0010250056 2 3 Motor fix plate 0010100531 1 30 Connecting rod 0010250062 3 4 Swing 001A13011049 4 31 Coupler 0010250063 6 5 Ventilate duct 0010201129 1 32 Connection 0010250064 8 6 Centrifugal fan 0010250024 1 33 Ambient temp.
MODEL : AB092FCAHA AB142FCAHA
Parts list No.
Parts list No.
Parts list No.
Model: AC142FCBHA / AC182FCBHA / AC182FCAHA
AC142FCBHA / AC182FCBHA No.
Parts list No. Spare parts number Spare parts description in English the proportion of the spare-part Price list($) Failure rate stock Remark Qty. Model 1 001A0100330 air inlet grill 1 AC182FCAHA 2.96 0.0000% 0.0000% × 2 001A2400087 air filter 2 AC182FCAHA 0.82 0.0000% 0.0000% × 3 001A1301395 teinforced rod 1 AC182FCAHA 0.44 0.0000% 0.0000% × 4 001A1431559 pinch plate 1 AC182FCAHA 0.00 0.0000% 0.0000% × 5 001A17001180 fixed board 1 AC182FCAHA 0.23 0.0000% 0.
Model: AD142FCBHA / AD182FCBHA
AD142FCBHA / AD182FCBHA NO.
Model: AE092FCAHA / AE092FCBHA / AE182FCAHA / AE182FCBHA
AE092FCAHA No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 / AE182FCAHA Specialized Number ------------------------------------------001A3400197 --------------0010400158 --------------0010400159 ----------------------------001A13011199 001A4000177 0010450059 001A5745116 0010100417 ------------------------------------------0010500725 AE182FCAHA 13 0010400297 Name Centrifugal fan Snail shell Fan motor Wired remote controller Heat exchanger Liquid pipe temp.
AE092FCBHA No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 / AE182FCBHA Specialized Number ------------------------------------------001A3400196 --------------0010400158 --------------0010400159 ----------------------------001A13011199 001A4000177 0010450059 001A5745116 0010100417 ------------------------------------------0010500725 AE182FCBHA 13 0010450401 Name Centrifugal fan Snail shell Fan motor Wired remote controller Heat exchanger Liquid pipe temp.
Model: AE092FCAKA / AE182FCAKA
AE092FCAKA No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 / AE182FCAKA Specialized Number ------------------------------------------001A3400197 --------------0010400158 --------------0010400159 ----------------------------001A13011199 001A4000177 0010450059 001A5745116 0010100417 ------------------------------------------0010500725 AE182FCAKA 13 0010400297 Name Centrifugal fan Snail shell Fan motor Wired remote controller Heat exchanger Liquid pipe temp.
MODEL : AF092FCBHA / AF122FCBHA
AF092FCBHA / AF122FCBHA NO.
MODEL : AP182FAAHA / AP182FABHA
AP182FAAHA No.
21 10 9 16 18 20 28 14 15 26 17 11 5 4 24 19 7 25 12 2 27 3 8 13 6 23 22 1 Model: AS092FMAHA AS092FMBHA
AS092FMAHA / AS092FMBHA No. Specialized Number 1 001A3400130 2 001A3300081 3 001A3900051 4 001A1431372 5 001A3900059 6 001A3800002 7 001A4000159 8 001A4400469 9 001A0100944 10 001A1232075 11 001A0100206 12 001A1431371 13 001A3000052 14 001A2335028 15 001A0300005 16 001A0900107 17 001A3000040 18 001A1232077 19 001A0900011 001A0400140 20 001A2400060 (left) 001A2400061 (right) 21 22 001A1431365 23 001A1431368 Name Controller assy.
1 2 3 4 32 33 34 31 30 29 5 28 35 6 27 36 7 37 38 26 8 25 39 9 40 10 42 41 43 24 23 22 21 11 12 13 14 20 19 18 17 16 15 Model: AS122FBBHA AS182FTAHA AS182FTBHA
Parts list No.
AS182FTAHA / AS182FTBHA No.
Sincere Forever