Important for installations in wet internal conditions or outdoors
Please note that trouble free operation can only be ensured if all the measures set
out below are carried out. The motor terminal box is to be fitted so that the cable
entries are directed downwards. Use suitable conduit screw fittings for the cable
being used and if necessary use reducing nipples. Conduit screw fittings and plugs
are to be coated with sealing compound, tightened up securely and recoated.
Cableintakes are also to be made completely watertight. The sealing surfaces of
terminal boxes and terminal box covers are to be properly cleaned before
reassembly. Gaskets are to be glued down on one face. Brittle gaskets are to be
replaced! When reassembling after maintenance work, etc. the end shield centering
spigots are also to be coated with sealing compound. The corrosion protection
consists of a number of paint coatings. Depending on environmental conditions the
paint coating must be renewed on a regular basis or wherever necessary. The stated
rated motor power applies for a maximum 40 °C ambient temperature and
installation altitude up to1000 m (3330 feet) above sea level.
For higher ambient temperatures or installation at greater heights the power rating is
reduced accordingly. (Refer to DIN 57530). The unimpeded access of ventilating
cooling air must be ensured. Condensate water drain holes (only on customer's
request) are plugged with plastic plugs that can be opened as required. Open
condensate water drain holes are not permitted because then the enclosure IP44
resp. IP55 is lost!