Specifications
Parameters/address space
4.1 Parameter
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
18 Manual, 04/2015, A5E03485935-AE
4.1.3
Parameters of the Counting mode
Parameters of the DI 32x24VDC HF Count in the Counting mode
If you want to use the module for counting, you need to set the module parameters as DI
32x24VDC HF Count. For channels 0 and channel 1, the following parameter settings are
then possible. For channels 2 to 31, the parameter settings apply as with the DI 32x24VDC
HF, , see section Parameters DI mode (Page 16).
Table 4- 2 Settable parameters and their defaults in the Counting mode
Parameter
Range of values
Default setting
Parameter
reassignment
in RUN
Range of effectiveness with con-
figuration software, e.g. STEP 7
Integrated in the
hardware catalog
as of STEP 7,
V13 SP1 with
HSP 0118 or
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Diagnostics
• No
supply voltage L+
Yes/No No Yes Channel* ---
• Wire break
Yes/No No Yes Channel ---
Input delay
0.05 ms, 0.1 ms,
0.4 ms, 1.6 ms, 3.2 ms,
12.8 ms, 20 ms
3.2 ms;
for isochronous
mode 0.05 ms
(cannot be changed)
Yes Channel ---
Hardware interrupt
• Disable
• Comparison event
occurred for DQ
Disable Yes Channel ---
Set output DQ
• Between a compar-
ison value and the
high counting limit
• Between a compar-
ison value and the
low counting limit
Between a compari-
son value and the
high counting limit
Yes Channel ---
Edge selection
• On rising edge
• On falling edge
•
On rising and falling
edge
On rising edge Yes Channel ---
High counting limit
0 ... 4294967295
4294967295
Yes
Channel
---
Comparison value
0 ... 4294967295**
1
Yes
Channel
---










