Specifications
140 IBM Flex System p260 and p460 Planning and Implementation Guide
Power cabling: 60A at 208V 3-phase (North America)
In North America, this configuration requires four 60A 3-phase delta supplies at
200 - 208 VAC, so an optimized 3-phase configuration is shown in Figure 5-8.
Figure 5-8 Example power cabling 60 A at 208 V 3-phase configuration
5.6.3 Chassis power supplies
The number of power supplies required depend on the number of nodes installed
within a chassis and the level of redundancy required. When installing additional
nodes, the power supplies are installed from the bottom upwards.
A maximum of six power supplies can be installed in the IBM Flex System
Enterprise Chassis. The power supplies are 80 PLUS Platinum certified and are
2500 W output, rated at 200 VAC, with oversubscription to 3538 W output at
200 VAC. The power supplies also contain two independently powered 40 mm
cooling fans.