3.5.2 Switch and Chassis Management Module cooling
There are two additional cooling zones for the I/O switch bays. These zones,
zones 3 and 4, are on the right and left side of the bays, as viewed from the rear
of the chassis. Cooling zones 3 and 4 are serviced by 40 mm fan modules that
are included in the base configuration and cool the four available I/O switch bays.
Upon hot-swap removal of a 40 mm fan module, an opening is exposed to the
80 mm fan modules located below, and a back flow damper in the fan bay
closes. The backflow damper prevents hot air from entering the system from the
rear of the chassis. During the time when the fan module is being replaced, the
80 mm fan modules cool the switch modules and the Chassis Management
Module. Figure 3-8 shows cooling zones 3 and 4 that service the I/O switch
modules.
Figure 3-8 Enterprise Chassis switch module and Chassis Management Module cooling
zones 3 and 4
3.5.3 Power supply cooling
The power supply modules have two integrated 40 mm fans. Installation or
replacement of a power supply and fans is done as a single unit.
The integral power supply fans are not dependent upon the power supply being
functional. Rather, they are powered independently from the midplane.