2.10.2 Mains connection up to 22kW (PE/L1/L2/L3)
No special safety devices are required on the mains input side for
the frequency inverter, just the normal mains protection (see
technical data) and a master switch/fuse.
Connection terminals cross-section:
SK 700E-151-340-A ...
SK 700E-751-340-A VDE 4mm² (0.5 … 0.6Nm)
UL/cUL (AWG 24-10)
SK 700E-112-340-A ...
SK 700E-152-340-A VDE 10mm² (1.2 … 1.5Nm)
UL/cUL (AWG 22-8)
SK 700E-182-340-A ...
SK 700E-222-340-A VDE 25mm² (2.4 … 4.0Nm)
UL/cUL (AWG 16-4)
Note: The use of this inverter on an IT network is possible
after minor alterations. Please consult your supplier.
2.10.3 Mains connection from 30kW (PE/L1/L2/L3)
No special safety devices are required on the mains input side for
the frequency inverter, just the normal mains protection (see
technical data) and a master switch/fuse.
Connection terminals cross-section:
SK 700E-302-340-O ...
SK 700E-372-340-O VDE 35mm² (6 … 8Nm)
(PE terminals = 16mm
2
) UL/cUL (AWG 2)
SK 700E-452-340-O ...
SK 700E-552-340-O VDE 25-50mm² (6 … 8Nm)
UL/cUL (AWG 4-0)
SK 700E-752-340-O … VDE 95mm² (15 … 20Nm)
SK 700E-902-340-O UL/cUL (AWG 000)
SK 700E-113-340-O ...
SK 700E-163-340-O VDE 50-150mm² (25 … 30Nm)
(PE terminals = 35-95mm
2
) UL/cUL (AWG 0-300 MCM)
Note: The use of this inverter on an IT network is possible
after minor alterations. Please consult your supplier.
Note: Only one PE terminal is located near the mains connection in the 90kW
device. Further PE connections can be implemented on the device housing.
PE
L1
L2
L3
M
3 ~
L3
L2L1
PE
Input
+B -B
Brake
-DC
PE
W
U V
Output
Brake resistor
Optional, Chap. 2.7/2.8
Brake resistor
Optional, Chap. 2.7/2.8
Some of the PE connections are in the support
plate, near to the terminal bar
Do not use ZW, the
connection is sealed.