Specifications
Cat 604-5 25
Dimension Drawings
Marine Water Box Dimensions
Marine water boxes with removable end covers are an available option on all evaporator and condenser sizes.
Figure 18: Marine Water Box Dimensions with Victaulic or Flanged Connections
Table 5: Marine Waterbox Dimensions - Flanged Connections
Table 6: 150 Class ANSI Flange Connection Dimensions (Detail from Figure 18)
sales office for certified drawings for unit-specific configuration and dimensions. Table
4:
Marine Waterbox Dimensions - Victaulic Connections
Diameter 1 PASS 2 PASS 3 PASS
Return
Head
Evap AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF UU
E30 14.00 21.00 27.75 26.50 13.25 10.75 21.00 27.75 26.50 13.25 8.13 21.00 6.63 21.00 27.75 26.50 13.25 10.19 9.78
E36 16.00 24.00 43.50 42.00 21.00 12.75 24.00 29.50 28.00 14.00 9.75 24.00 8.63 24.00 29.50 28.00 14.00 11.81 11.26
Cond AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF UU
C26 10.75 19.00 21.25 20.00 10.00 8.63 19.00 21.25 20.00 10.00 7.07 19.00 6.63 19.00 21.25 20.00 10.00 8.07 8.38
C30 14.00 21.00 27.75 26.50 13.25 10.75 21.00 27.75 26.50 13.25 8.13 21.00 6.63 21.00 27.75 26.50 13.25 10.19 9.78
C36 16.00 24.00 43.50 42.00 21.00 12.75 24.00 29.50 28.00 14.00 9.75 24.00 8.63 24.00 29.50 28.00 14.00 11.81 11.26
Diameter 1 PASS 2 PASS 3 PASS
Return
Head
Evap AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF UU
E30 14.00 21.50 27.75 26.50 13.25 10.75 21.50 27.75 26.50 13.25 8.13 21.50 6.63 21.50 27.75 26.50 13.25 10.19 9.78
E36 16.00 24.50 43.50 42.00 21.00 12.75 24.50 29.50 28.00 14.00 9.75 24.50 8.63 24.50 29.50 28.00 14.00 11.81 11.26
Cond AAA BBB CCC DDD EEE AAA BBB CCC DDD EEE FFF GGG AAA BBB CCC DDD EEE FFF UU
C26 10.75 19.50 21.25 20.00 10.00 8.63 19.50 21.25 20.00 10.00 7.07 19.50 6.63 19.50 21.25 20.00 10.00 8.07 8.38
C30 14.00 21.50 27.75 26.50 13.25 10.75 21.50 27.75 26.50 13.25 8.13 21.50 6.63 21.50 27.75 26.50 13.25 10.19 9.78
C36 16.00 24.50 43.50 42.00 21.00 12.75 24.50 29.50 28.00 14.00 9.75 24.50 8.63 24.50 29.50 28.00 14.00 11.81 11.26
Nozzle
Dia.
Drawing & Dimension Notes:
1 Dimensions in inches.
2 Flanges are ANSI raised face. Mating flanges by others.
3 Some condensers with flanges can have staggered connections due to flange interference.
Consult factory.
4 Flanges add 0.5 inches to the distance from the vertical centerline to the flange face compared
to Victaulic.
VV WW XX YY ZZ
6.63 11.00 1.56 8.00 0.88 9.50
8.63 13.50 1.75 8.00 0.88 11.75
10.75 16.00 1.94 12.00 1.00 14.25
12.75 19.00 2.19 12.00 1.00 17.00
14.00 21.00 2.25 12.00 1.12 18.75
16.00 23.50 2.50 16.00 1.12 21.25
ON "ZZ" BOLT CIRCLE
"XX" HOLES, "YY" DIAMETER
TYPICAL 150 CLASS ANSI
FLANGE CONNECTION
NOTE: FLANGE BOLT HOLES MUST STRADDLE
VERTICAL CENTERLINE ON CONNECTIONS
WW
VV
STANDARD RETURN HEAD FOR
EVAPORATOR AND CONDENSER
UU
*BBB
AAA
EVAPORATOR, 1 PASS
ALL UNITS
*BBB
*GGG
FFF TYP.
AAA
EVAPORATOR, 2 PASS
UNITS WITH 3/4" TUBING
AAA
*BBB
FFF
EVAPORATOR, 3 PASS
UNITS WITH 3/4" TUBING
OUTLET HEAD POSITION
ON OPPOSITE END OF UNIT
EEE
DDD
CCC
DDD
EEE
CCC
OUT
IN
EEE
DDD
CCC
IN
TYP.
FFF
AAA
*GGG
*BBB
EVAPORATOR, 2 PASS
UNITS WITH 1" & MIX TUBING
EEE
DDD
CCC
OUT
IN
*BBB
AAA
CONDENSER, 1 PASS
*GGG
*BBB
TYP.
FFF
AAA
CONDENSER, 2 PASS
AAA
TYP.
FFF
*BBB
CONDENSER, 3 PASS
OUTLET HEAD POSITION
ON OPPOSITE END OF UNIT
EEE
DDD
CCC
EEE
DDD
CCC
IN
OUT
EEE
DDD
CCC
IN
NOTE: * - ADD .500 INCH FOR FLANGED CONNECTION
(SEE DETAIL LOWER LEFT)
EVAPORATOR MARINE WATER BOX SELECTION
CONDENSER MARINE WATER BOX SELECTION
NOTE: * - ADD .500 INCH FOR FLANGED CONNECTION
(SEE DETAIL LOWER LEFT)
RIGHT END REPRESENTATIVE VIEW
( TYPICAL OF ALL STACKS WITH 2 PASS
HEADS & 3/4" EVAP TUBES )
Note: On certain models connection dimensions may vary; some models will have rear-facing MWB connections. Consult your local Daikin