Specifications

Corporate - 29395 Wall St. Wixom, MI 48393
West MI - 2385 Wilshere Drive Jenison, MI 49428
800.419.5199 Fax: 248.374.6408
Got Power? Generator Sales, Service & Rental
BILL OF MATERIAL
(2) BALDOR 350 KW DIESEL GENERATORS
Model
Engine Manufacturer
Frequency / Speed (RPM)
Ambient (Min/Max)
IDLC350-3DU
Detroit
60 Hz / 1800
-18 °C / 40 °C
Duty / Alt Temp Rise
Engine Model
Engine Control Voltage (DC)
Elevation
Standby / 105 °C
6063HV35
24
1000 Ft
Genset Agency Approval
Emissions Standard
Fuel Type
Enclosure / Mount Method
UL2200 / CUL
Tier 3 Emergency
Diesel
Enclosed / Skid Mounted
Output Rating (kw/kva)
Full Load Amps
Voltage (L-L/L-N) - Connection
Phase / Power Factor
350 KW / 438 KVA
526A
480/277 - Hi Wye
Three / 0.80
Additional Specifications:
PRODUCT
Emissions Application:
EPA Stationary Emergency
ALTERNATOR
Alternator Regulator:
MX341-UL
Drip shield:
IP22
Alternator Excitation:
PMG
Alternator Model Number:
HCI434F-311
Alternator Agency Approval:
UL1004
ENGINE
Engine Governor Type:
Engine Mfr ECU
Oil and Coolant Drains:
Yes
Coolant Radiator:
Unit mounted
Coolant Heater:
2.5kW 240V 1Ph w/ J-Box
Battery:
Standard Starting
Battery Quantity:
2
Battery Type:
Group8D Style 12V 1100 CCA Min
Battery Charger:
Yes
BC Brand:
Stored Energy Systems
BC Battery Type:
Lead Acid
BC Output Amps:
10A
BC Input Volts & Hertz:
120/60
CONTROL
Genset Controller:
InteliGen NT Digital Controls (Internet Module, Monitoring Panel)
Controller Voltage Adjustment:
Yes
Controller Low Coolant Level:
Yes
NFPA110 Level 1 version:
Yes
Run Relay:
Yes
Louver Relay:
Yes
Remote Annunciator:
Surface Mounted RA-15
Remote E-Stop:
Yes
Remote Genset Display:
Yes
Paralleling version:
Yes
ENCLOSURE
Enclosure Style:
Sound Attenuated (79 dba @ 23’)
Enclosure material:
Aluminum - Pre Painted
Enclosure color:
Baldor Almond - C11
Enclosure Logo:
Standard Baldor Logo
Enclosure Hardware Kit:
Stainless Steel HW Key-lockG3A
Intregrated Vibro Mounts:
Included
EXHAUST
Exhaust Attenuation Grade:
Critical
Exhaust Mounting Method:
Internal mount for enclosure
POWER CONNECTION
Circuit Breaker:
1
1 Circuit Breaker Rating:
100% Electronic Adjustable (Motorized)
1 Circuit Breaker Amp:
600A
1 Circuit Breaker Volt Frame:
600
1 Circuit Breaker Pole:
3 Pole
1 Circuit Breaker Mount Loc.:
Unit mounted
1 Circuit Breaker Aux Switch:
1 FORM C
1 Circuit Breaker Shunt Trip:
Yes
FUEL
Fuel Tank Capacity:
250 Gallons
Fuel Tank Type:
Steel Double Wall Day Tank
Fuel Tank Agency Approval:
UL-142 / MDEQ
Flex Fuel Lines:
UL
UL 2200 RATING SHALL BE FOR ENTIRE
PACKAGED UNIT
FLODDED CELL TYPE PER
263213D,2.3,J,4
COMPLY WITH APPLICABLE STATE AND
LOCAL GOVERNMENT NOISE LEVEL 2 PER
63213D,1.5,I
COORDINATE FINAL COLOR WITH
OWNER PER 263213D,2.12,A
HOSPITAL GRADE/CRITICAL PER
263213D,2.3,H
COMPLY WITH UL489 PER
263213D,2.8,A
Yes it is
GROUP 8D 12V 1155 CCA /
FLOODED CELL TYPE BATTERIES
Spec calls out 85 dba or less. I'm not
sure what the local code is, but I'm
sure we meet it.
Hospital Grade Silencer is a Critical
Grade Silencer with Baldor
Almond is our
standard color. Please
notify PMT before
final approval
We are compliant