Specifications

Controls
AC input voltage select Field-selectable switch
Optional 12/24-volt output select Field-selectable two-position jumper
Battery program select Field-selectable six-position jumper
Fast charger enable/disable Field-selectable two-position jumper
Temp compensation enable Standard. Can be disabled or re-enabled in the  eld
Remote temp comp enable Connect optional remote sensor to temp comp port
Environmental
Operating temperature -20C to +60C, meets full speci cation to +45C
Over temperature protection Gradual current reduction to maintain safe power device temperature
Humidity 5% to 95%, non-condensing
Vibration (10A unit) UL 991 Class B (2G sinusoidal)
Transient immunity ANSI/IEEE C62.41, Cat. B, EN50082-2 heavy industrial
Agency Standards
Safety C-UL listed to UL 1236 (required for UL 2200 gensets), CSA standard 22.2
no. 107.2-M89
CE: 50/60 Hz units DOC to EN 60335
Agency marking 60 Hz: C-UL-US listed
50/60 Hz: C-UL-US listed plus CE marked
EMI FCC Part 15 Class B; EN 50081-2
NFPA standards NFPA 70, NFPA 110. (NFPA 110 requires Alarms “C”)
Optional agency compliance Units with Alarms “1” con guration available with additional compliance to UL
category BBHH and NFPA 20
Construction
Housing/con guration Material: Heavy clear anodized aluminum. Con guration options:
• Fully enclosed: C-UL listed enclosure
• Open frame: C-UL recognized
• Slimline: C-UL recognized open frame construction with remote isolation transformer
Packaging Open-frame and Slimline con gurations only available in bulk OEM quantities and packaging
Dimensions See Drawings and Dimensions page for details
Printed circuit card Surface mount technology, conformal coated
Cooling Natural convection
Protection degree Listed housing: NEMA-1 (IP20). Optional NEMA 3R enclosure
Damage prevention Fully recessed display and controls
Electrical connections Compression terminal blocks
Warranty
Standard warranty Three year parts and labor warranty from date of shipment
Optional warranty If speci ed at time of order, warranty coverage is increased to reimburse customer’s documented
eld service costs up to the original charger price. Contact the factory for full details
Optional features
Input Input frequency, 50/60 Hz
Remote temp comp sensor Recommended where battery and charger are in different locations
Drip shield Protects from dripping water
NEMA 3R housing Enables outdoor installation (remote temp sensor recommended)
UL BBHH listing Available in 10A units with Alarms “1”
Field service warranty Reimbursement of customer  eld service expenses
up to charger price
Simple  eld
adjustments