Specifications

Diesel
Diesel
IDLC350-3D
Diesel
Diesel
Genset Ratings
Ratings Range 60 Hertz Operation
Standby: kW 200 - 350
kVA 200 - 438
Prime: kW 185 - 320
kVA 185 - 400
Baldor generators are available in a variety of power ratings
and installation styles to meet the energy needs of the
smallest businesses and the largest manufacturing facilities.
All generator sets are designed to meet the specications
to ensure the fastest startup and dependable long-term
operation. Rely on Baldor generators to provide the
clean, quiet and environmentally friendly electrical power
when you need it most. Emergency backup, standby,
prime power, peak shaving or for any of your day or night
electrical power needs, you can count on a dependable
Baldor generator to provide the peace of mind and security
you desire.
Standby and Prime Power Features
4 Heavy-duty industrial diesel engine that meets the latest
EPA emissions levels
4 Brushless synchronous alternators with dynamic
balancing and four pole construction
4 Fully featured microprocessor based controller that’s
easy to use and eld programmable for customized
installations
4 Generator sets are prototype tested and production
tested to ensure easy startup
4 Gen-set accepts rated load in one step
4 Heavy duty construction that’s designed for use in prime
or standby applications
4 Manufactured in a dedicated and secure ISO-9001
certied facility
4 Generator sets are backed by a world wide network of
parts and service centers
4 Optional agency approvals available including UL2200
and NFPA110
4 Optional environmental enclosures available including
weather resistant, sound attenuated, containerized, and
walk-in models
4 Full range of genset accessories and factory installed
options available
Genset
Model Number
Alternator
Voltage
L-N / L-L
Phase Hertz
150°C Rise
Standby Rating
125°C Rise
Prime Rating
kW / kVA Amps kW / kVA Amps
IDLC350-3D HCI444E-311
120/208 3 60 325/406 1129 305/381 1059
(1) 120/240 3 60 325/406 978 305/381 918
(1) 120/240 1 60 200/200 833 185/185 771
139/240 3 60 350/438 1054 320/400 963
220/380 3 60 296/370 563 276/345 525
277/480 3 60 350/438 527 320/400 482
HCI444E-17
347/600 3 60 350/438 421 320/400 385
HCI444F-311
120/208 3 60 350/438 1216 320/400 1112
(1) 120/240 3 60 350/438 1054 320/400 963
(1) 120/240 1 60 230/230 958 210/210 875
139/240 3 60 350/438 1054 320/400 963
220/380 3 60 344/430 654 320/400 608
277/480 3 60 350/438 527 320/400 482
HCI444F-17
347/600 3 60 350/438 421 320/400 385
NOTES: (1) Alternator connections have two circuits available for low voltage.
Available current in each low voltage circuit is equal to high voltage current listed in table.
For ratings and voltages not listed above refer to the Genset Selector.
Standby ratings do not have an overload capability but can be used for the duration of the utility failure per ISO-3046, DIN6271 and BS5514.
Prime (Unlimited Running Time) ratings are continuous per DIN 6271 and ISO-3046 with 10% overload capacity.
Baldor reserves the right to implement specifications or design changes without notice.
We changed the Alternator to
HCI434F - 105 Degree C Rise