Specifications
Powerpact M-Frame
Circuit Breaker Accessories
Shunt Trip (various AC and DC
voltages are available)
Undervoltage Trip (various AC and DC
voltages are available)
Time Delayed Undervoltage Trip
(various AC and DC voltages are
available)
Auxiliary Switches (up to 3A/3B
switches); Low-level (Volts and Amps)
switches are also available
Alarm Switch (1A/1B); Low-level
(Volts and Amps) switch is also
available
Standard Mechanical Lug (aluminum
or copper)
Crimp (compression) Lug (aluminum
or copper)
Power Distribution Lug (aluminum)
Bus Connector Kit
Inter-Phase Barriers
Door Escutcheons (for toggle or
accessory cover)
Padlocking Device (removable or fixed
version)
Key-lock Device (Kirk or Federal
Pioneer)
Powerpact
®
M-Frame Molded Case Circuit Breakers
Contact your Square D® sales
representative for additional information.
Or, visit www.us.squared.com
03-04
Order Number 0612HO0401
Schneider Electric - North American Operating Division
1415 S. Roselle Road
Palatine, IL 60067
Tel: 847-397-2600
Fax: 847-925-7500
Features
Square D
®
MA/MH
Square D
Powerpact M
Square D
Powerpact P
Amp Rating
300A – 1200A 300A – 800A 250A – 1200A
2P and 3P
Yes Yes Yes
Interrupting
Rating (kA)
(240/480/600 V)
MA: 42/30/22
MH: 65/65/25
G: 65/35/18
J: 100/65/25
G: 65/35/18
J: 100/65/25
K: 65/50/50
L: 125/100/-
Dual Rated
UL489/ IEC 947-2
Yes Yes Yes
Trip Unit
Protection
Thermal-Mag
(fixed Thermal)
LI (fixed long time
pick-up)
LI/LSI/LSIG
Trip Unit Power
Measurement
No
No Yes
Trip Unit
Communication
No No Yes (Modbus –
open protocol)
Interchangeable
Trip Units
No
No
Yes
80/100% Rating
80% 80% 80 or 100%
Motor Operator/
Electrically Operated
Yes No Yes
Drawout
No No Yes
Dimensions (inch)
H x W x D
14 x 9 x 5
12.8 x 8.3 x 5.8
12.8 x 8.3 x 5.8
Weight (lbs.)
34 30 32
Features Comparison
© 2005 Schneider Electric All Rights Reserved
PowerpactMhandout 2/2/05 8:55 AM Page 2