BILL OF MATERIAL FOR THE DAY TANK’s
Quantity
Description
(2)
SB20 - 250 Gallon Free Standing Day Tank
UL #142 Listed
Standard Features
Quantity
Part #
Tank Dim: 39"H x 50"W x 54"L Wt: 1250#
1
DW-101
Double Wall Secondary Containment
1
3650
Dip Tube Supply/Return Fitting Package (1/2” NPT)
1
4300
Fuel in Basin Alarm (2" NPT, top mounted)
1
3502
Basin Drain (1/2” NPT)
1
3005
Locking Manual Fill Cap
1
1001
Krueger Fuel Level Gauge (2" NPT, swing arm)
1
3152
Standard Vent Cap (2” NPT)
2
3163
Emergency Pressure Relief Cap (3” NPT)
4
8410
Flush Mount Lifting Plate (minimum 4)
1
Black
Paint Color Black
Options Included:
2
8310
C-Channel Basin Support per MDEQ (C8 x 11.5)
1
NFPA
NFPA Diamond Hazardous Material Decal for Diesel Fuel
1
700-0007
Label - Diesel Fuel Only
1
700-0009
Label - Combustible Liquids
1
Special
Label – Keep Fire Away
1
1060
(2) alarm panel mounted on day tank (Normal full & high level)
1
1099
Low/Pump On/Pump Off/High Float Assembly
1
1098
Lag Float (Set at 11") (For #2 supply pump control)
1
2010
Reverse Pumping System (pump mounted on day tank top)
1
6070
7 gpm Self Priming Pump, 3/8" Ports, 1/2 HP Motor 115 VAC
1
3600
1/2" Diptube (7" Long)
2
3195
Extra Piping Connection w/Plug (2" NPT) Spare
NOTE: This day tank includes a float sender to send signals to an existing Simplex pump controller, which controls
existing duplex supply pumps. This controller must also control the reverse pump being supplied with this day tank.