Specifications
Alternator Specifications
Alternator Specifications
Genset Controller Specifications
Genset Controller Specifications
Alternator Type 4-Pole, Rotating Field
Exciter Type Brushless
Excitation System PMG
Insulation per NEMA MG1
Material Class H
Standby Temp Rise 150˚C
Prime Temp Rise 125˚C
Lead Connection 12 Lead, Reconnectable
Stator Pitch 2/3
Amortisseur Winding Full
Bearing Single, Double Shielded
Drive Coupling Flexible Disk
Unbalanced Load 20% of Standby Rating
Baldor InteliLite NT Features
Large back-lit graphical LCD Display
64x128 pixel resolution
6 LED Genset Status Indicators
Alarm Red LED
Not In Auto Red LED
Warning Yellow LED
Running Green LED
Ready / Auto Green LED
Supplying Load Green LED
Sealed Membrane Panel to IP65
Push Buttons for Simple Control
Start, Stop, Fault Reset, Horn Reset, Mode,
Page, and Enter Keys
Display Metering and Protection
Oil Pressure Warning / Shutdown
High/Low Coolant Temperature Warning
High Coolant Temperature Shutdown
Low Coolant Level Shutdown
Low Fuel Level Warning / Shutdown
Over Speed Protection
Battery Voltage Under/Over Warning
Running Hour Meter
Generator Under/Over Volts Warn/Shutdown
Generator Under/Over Freq Warn/Shutdown
Generator Over Current Shutdown
Generator Output Metering for V1-V3, I1-I3,
Hz, kW, kWh, kVAr, kVAh
Automatic Voltage Regulator
PMG Std MX341, Opt MX321
Voltage Regulation No Load to Full Load
PMG Regulator +/- 1%, +/- 0.5%
Load Acceptance 100% of Rating,
One Step
Subtransient Reactance
480V, Per Unit 12%
TIF (1960 Weighting) <50
Line Harmonics 5% Maximum
Motor Starting kVA 30% Max Voltage Dip
Alt @ 480V SkVA HCI444E-311 - 1040
Alt @ 480V SkVA HCI444F-311 - 1260
NFPA110 Compliance
An optional Remote Annunciator is available
to meet NFPA110 applications
Remote Annunciator Features – RA15
15 LED Indicators with Function Labels
Horn Reset and Lamp Test keys
CAN Bus Connection for up to 600 Feet
Changed to 105 Degree C Rise