Specifications

Enclosure Packages
Standard/Basic
Applicable to all models
above 250 kW
14 gauge steel ASTM
A569, #4 finish
Optional 0.080, 5052
Aluminum
Modular construction –
full flexibility
Powder paint system
Weather Resistant drip
proof construction
Heavy duty door gaskets
2 or 4 side access doors
Heavy duty latch assembly
Heavy duty lockable
handle
Heavy duty stainless steel
hinge with brass pin
Pre-hung door assemblies
Fixed intake louvers
Structural base
Radiator cap access
Rain gutter over all doors
and openings
Applicable to all models
20 - 250 kW
Same as above
except following:
Doors are lift-off not
hinged
Standard duty latch
assembly
Punched intake screen
Formed steel base
Mounting to Gen-set
* Internally mounted silencer
may affect ambient
performance and
enclosure dimensions
Basic Attenuation
Applicable to all models
above 250 kW
14 gauge steel ASTM
A569, #4 finish
Optional 0.080, 5052
Aluminum
Interior walls lined with
acoustical foam
Modular construction-full
flexibility
Powder paint system
Weather Resistant drip
proof construction
Heavy duty door gaskets
2 or 4 side access doors
Heavy duty latch assembly
Heavy duty lockable
handle
Heavy duty stainless steel
hinge with brass pin
Fixed intake louvers
Structural base
Radiator cap access
External radiator discharge
hood with screen
Rain gutter over all doors
and openings
Applicable to all models
20 - 250 kW
Same as above
except following:
Doors are lift-off not
hinged
Standard duty latch
assembly
Punched intake screen
Formed steel base
Mounting to Gen-set
* Internally mounted silencer
may affect ambient
performance and
enclosure dimensions
** Basic noise reduction dbA
level not available
Sound Attenuated
HPE Level One
Specification Available
Upon Request
Applicable to all models
above 900 kW
15 dbA noise reduction at
3 meters
14 gauge steel ASTM
A569, #4 finish
Optional 0.080, 5052
Aluminum
Modular construction-full
flexibility
Powder paint system
Weather Resistant
drip proof construction
Heavy duty door gaskets
2 or 4 side access doors
Heavy duty latch assembly
Heavy duty lockable
handle
Heavy duty stainless steel
hinge with brass pin
Pre-hung door assemblies
Sound deadening interior
wall construction
Interior surfaces lined with
perforated mill finish
aluminum
Acoustic Intake louvers-
fixed, aluminum
Internal discharge hood
Radiator cap access
Mounting to frame or tank
Exhaust system required –
not included **
Rain gutter over all doors
and openings
3" Wall construction
Isolators required - not
included
• Shipping supports – Field
adjustable
Applicable to all models
30 - 825 kW
Same as above
except following:
External radiator discharge
hood with scr
een
* Internally mounted silencer
may affect ambient
performance and
enclosure dimensions
**Must be Critical Grade at
minimum
Sound Attenuated
HPE Level Two
Specification Available
Upon Request
Applicable to all models
above 500 kW
25 dbA noise reduction at
3 meters
14 gauge steel ASTM A569,
#4 finish
Optional 0.080, 5052
Aluminum
Modular construction-full
flexibility
Powder paint system
Weather Resistant
drip proof construction
Heavy duty door gaskets
2 or 4 side access doors
Heavy duty latch assembly
Heavy duty lockable handle
Heavy duty stainless steel
hinge with brass pin
Pre-hung door assemblies
Sound deadening interior
wall construction
Acoustic composite barrier
material
Interior surfaces lined with
perforated mill finish
aluminum
Insulated Intake air hoods
Acoustic Intake louvers-
fixed, aluminum
Internal discharge hood
Radiator cap access
Mounting to frame or tank
Exhaust system required –
not included **
Rain gutter over all doors
and openings
3" Wall construction
Isolators required - not
included
• Shipping supports – Field
adjustable
Applicable to all models
30 - 450 kW
Same as above
except following:
External Insulated radiator
discharge hood with screen
* Internally mounted silencer
may affect ambient
performance and enclosure
dimensions
**Must be Critical Grade at
minimum
Sound Attenuated
HPE Level Three
Specification Available
Upon Request
Applicable to all models
40 dbA noise reduction at 3
meters
14 gauge steel ASTM A569,
#4 finish
Optional 0.080, 5052
Aluminum
Modular construction-full
flexibility
Powder paint system
Weather Resistant
drip proof construction
Heavy duty door gaskets
2 or 4 side access doors
Heavy duty latch assembly
Heavy duty lockable handle
Heavy duty stainless steel
hinge with brass pin
Pre-hung door assemblies
Fixed intake louvers
Radiator cap access
Mounting to frame or tank
6" Wall construction
Sound deadening interior
wall construction
Acoustic composite barrier
material
Interior surfaces lined with
perforated mill finish
aluminum
Intake air attenuator
Interior vertical discharge
with attenuator.
Exhaust system required –
not included **
Rain gutter over all doors
and openings
Isolators required - not
included
• Shipping supports – Field
adjustable
* Internally mounted silencer
may affect ambient
performance and enclosure
dimensions
**Must be Super Critical
Grade at minimum
COMPLY WITH APPLICABLE STATE AND
LOCAL GOVERNMENT NOISE LEVEL 2 PER
63213D,1.5,I