Technical data

3–06 Operation
3.6 Stopping the engine in manual mode
Preconditions
Generator is not connected to network.
Engine is running in manual mode.
CAUTION
Stopping the engine when it is running at full load causes extreme stress to the engine.
Risk of overheating, damage to components!
Before stopping the engine, operate it at idle speed until operating temperatures decrease
and stable values are indicated.
Preparation
Item Task
Engine After the generator circuit breaker has been opened, allow the engine to cool
down by running it idle for approx. 5 minutes.
Stopping the engine
Item Task
Switching cabinet, control
panel etc. (depending on
manufacturer)
Press stop button.
Automatic stopping procedure is performed;
Engine is stopped.
After s topping the engine
Item Task
Cooling pump Operate for approx. 5 minutes after engine stop.
M015560/00E 03-05 ©MTU