Technical data
Troubleshooting 5–15
Fault code Alarm text Meaning Task
354 OPEN_LOAD
CYL. B4
Disconnection in wiring to
solenoid valve cylinder B4;
Misfiring
1. Check wiring.
2. Contact Service.
355 OPEN_LOAD
CYL. B5
Disconnection in wiring to
solenoid valve cylinder B5;
Misfiring
1. Check wiring.
2. Contact Service.
356 OPEN_LOAD
CYL. B6
Disconnection in wiring to
solenoid valve cylinder B6;
Misfiring
1. Check wiring.
2. Contact Service.
357 OPEN_LOAD
CYL. B7
Disconnection in wiring to
solenoid valve cylinder B7;
Misfiring
1. Check wiring.
2. Contact Service.
358 OPEN_LOAD
CYL. B8
Disconnection in wiring to
solenoid valve cylinder B8;
Misfiring
1. Check wiring.
2. Contact Service.
359 OPEN_LOAD
CYL. B9
Disconnection in wiring to
solenoid valve cylinder B9;
Misfiring
1. Check wiring.
2. Contact Service.
3
60
O
PEN_LOAD
CYL. B10
D
isconnection in wiring to
solenoid valve cylinder B10;
Misfiring
1. Check wiring.
2. Contact Service.
361 POWE
RSTAGE
FAIL 1
Defe
ct in ECU (solenoid valve
power stage)
Cont
act Service.
362 POWER STAGE
FAIL 2
Defect in ECU (solenoid valve
power stage)
Contact Service.
363 STOP POWER
STAGE
1
Solenoid valve or wiring or
ECU de
fective
automatic engine shutdown
1. Check wiring.
2. Try t
o re-start the engine
(→ Page 3 – 03).
3. Conta
ct Service.
364 STOP POWER
STAGE 2
Solenoid valve or wiring or
ECU defective
automa
tic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(→ Page 3 – 03).
3. Contact Service.
365 STOP
MV-WIRING
Solen
oid-valve wiring faulty;
automatic engine shutdown
1. Chec
k wiring.
2. Try to re-start the engine
(→ Pa
ge 3 – 03).
3. Contact Service.
381 TRAN.OUT1
PLANT DEF
Binary transistor output plant 1
defective
Contact Service.
382 TRAN.OUT2
PLANT
DEF
Binary transistor output plant 2
defec
tive
Contact Service.
383 TRAN.OUT3
PLANT DEF
Binary transistor output plant 3
defective
Contact Service.
384 TRAN.
OUT4
PLANT DEF
Binar
y transistor output plant 4
defective
Conta
ct Service.
M015560/00E 03-05 ©MTU