Operating instructions

Operation 3
Starting the engine
Item Task
Switching cabinet, control
panel etc. (depending on
manufacturer)
If coolant temperature is
> 40
C (with preheating pump), or
> 10
C (60 Hz generator, without preheating pump), or
>5
C (50 Hz generator, without preheating pump):
Press start button.
Automatic starting procedure is performed;
Tachometer indicates increasing crankshaft speed;
After the starting procedure is completed, engine is running at rated
speed.
Connecting the generator to network, running the engine to reach operating temperature
Item Task
Switching cabinet, control
panel etc. (depending on
manufacturer)
Close the generator circuit breaker.
Engine Run engine at 10 to 15 % of rated power to reach operating temperature.
Apply full load only after engine has reached operating temperature (coolant
temperature approx. 75
C).
3.4 Emergency start (override mode)
CAUTION
Safety functions and engine shutdown alarms will be disregarded.
Serious damage to plant!
Initiate emergency start only in emergency situations.
Preparation
Item Task
Operating mode selector switch
(if provided)
Change to manual mode.
Emergency start
Item Task
Switching cabinet, control
panel etc. (depending on
manufacturer)
Actuate switch/button for override input of ECU.
Switching cabinet, control
panel etc. (depending on
manufacturer)
Press start button.
Automatic starting procedure is performed; All safety functions are
deactivated and engine shutdown alarms disregarded;
Tachometer indicates increasing crankshaft speed;
After the starting procedure is completed, engine is running at rated
speed.