Operating instructions
Troubleshooting 15
Fault code Alarm text Meaning Task
354 OPEN_LOAD
CYL. B4
Disconnection in wiring to
solenoid valve cylinder B4;
Misfiring
1. Check wiring.
2. Contact Service.
355 OPEN_LOAD
CYL. B5
Disconnection in wiring to
solenoid valve cylinder B5;
Misfiring
1. Check wiring.
2. Contact Service.
356 OPEN_LOAD
CYL. B6
Disconnection in wiring to
solenoid valve cylinder B6;
Misfiring
1. Check wiring.
2. Contact Service.
357 OPEN_LOAD
CYL. B7
Disconnection in wiring to
solenoid valve cylinder B7;
Misfiring
1. Check wiring.
2. Contact Service.
358 OPEN_LOAD
CYL. B8
Disconnection in wiring to
solenoid valve cylinder B8;
Misfiring
1. Check wiring.
2. Contact Service.
359 OPEN_LOAD
CYL. B9
Disconnection in wiring to
solenoid valve cylinder B9;
Misfiring
1. Check wiring.
2. Contact Service.
360 OPEN_LOAD
CYL. B10
Disconnection in wiring to
solenoid valve cylinder B10;
Misfiring
1. Check wiring.
2. Contact Service.
361 POWER STAGE
FAIL1
Defect in ECU (solenoid valve
power stage)
Contact Service.
362 POWER STAGE
FAIL2
Defect in ECU (solenoid valve
power stage)
Contact Service.
363 STOP POWER
STAGE 1
Solenoid valve or wiring or
ECU defective
automatic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(
Page 3 2).
3. Conta
ct Service.
364 STOP POWER
STAGE 2
Solenoid valve or wiring or
ECU defective
automatic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(
Page 3 2).
3. Contact Service.
365 STOP
MV-WIRING
Solen
oid-valve wiring faulty;
automatic engine shutdown
1. Chec
k wiring.
2. Try to re-start the engine
(
Page 3 2).
3. Contact Service.
381 TRAN.OUT1
PLANT DEF
Binary transistor output plant 1
defective
Contact Service.
382 TRAN.OUT2
PLANT DEF
Binary transistor output plant 2
defective
Contact Service.
383 TRAN.OUT3
PLANT DEF
Binary transistor output plant 3
defective
Contact Service.
384 TRAN.
OUT4
PLANT DEF
Binar
y transistor output plant 4
defective
Conta
ct Service.
M015403/00E 02-09 © MTU
www.generent.ru