Operating instructions
Fuel system 21
6.7 Fuel system
6.7.1 Fuel system venting
Preconditions
Engine is stopped and starting disabled.
Material
Designation / Use Part No. Qty.
Diesel fuel
FLS
WARNING
Fuels are combustible.
Risk of fire and explosion!
Avoid naked flames, electrical sparks and ignition sources.
Do not smoke.
LP fuel system venting
1. Loosen flushing/return line of HP pump at
connection (1).
2. Unlock fuel priming pump (2), unscrew handle.
3. Operate the fuel priming pump (2) with the
handle until bubble-free fuel comes out of the
connection (1).
4. Lock fuel priming pump (2), screw in handle.
5. Verify that fuel priming pump (2) is locked:
Handle must be tightened.
6. Tighten connection (1) of flushing/return line.
M015403/00E 02-09 © MTU