Operating instructions

6.16.2 Differential pressure gauge – Check
WARNING
Fuels are combustible.
Risk of fire and explosion!
Avoid open flames, electrical sparks and ignition sources.
Do not smoke.
Differential pressure gauge – Check
1. Switch on fuel treatment system (→ Page 26).
2. Set the alarm points at the differential pressure gauge to zero.
Result: Alarm is initiated with preset delay.
3. Reset the alarm points at the differential pressure gauge to the specified values.
100 | Task Description | MS150095/01E 2012-08