Operating instructions

3.4 Checks prior to start-up
Checks prior to start-up
1. Check tank and the entire pipework for cleanness. If microorganisms are detected:
a) Clean affected components.
b) Disinfect affected components with biocides (→ MTU Fluids and Lubricants Specifications
A001061/..).
2. Close drain valves on housing.
3. Open all supply and discharge valves.
4. Switch on fuel treatment system (→ Page 29).
5. Check direction of rotation of pump.
6. Vent bypass and fuel lines of the system.
a) Open ball valve for pressure tank.
b) Open ball valve for overflow tank.
c) Close ball valve at the inlet to the fuel treatment system.
Result: Bypass line is vented via the overflow tank.
d) Open ball valve at the inlet to the fuel treatment system.
7. Check the fuel treatment system for leaks.
Result: The fuel treatment system is ready for operation.
MS150095/01E 2012-08 | Operation | 25
TIM-ID: 0000007736 - 005