Operating instructions

6.18.2 Differential pressure gauge – Check
WARNING
Fuels are combustible.
Risk of fire and explosion!
Avoid open flames, electrical sparks and ignition sources.
Do not smoke.
Checking differential pressure gauge
1. Switch on fuel treatment system (→ Page 73).
2. Set the alarm points at the differential pressure gauge to zero.
Result: Alarm is initiated with preset delay.
3. Reset the alarm points at the differential pressure gauge to the specified values.
MS150047/02E 2012-03 | Task Description | 169