3.6 Fuel treatment system control cabinet – Control elements
No. Color Caption Meaning/Function
1 Green Signal lamp Indicates „Pump running“
2 Red Signal lamp Indicates „Pump fault“
3 Yellow Illuminated but‐
ton
Indicates „Water drain“ / Press to drain water manually.
4 Red Illuminated but‐
ton
Indicates „Water alarm“ / Press to acknowledge.
5 Yellow Signal lamp Indicates „Filter warning“ due to increased differential pressure.
6 Red Illuminated but‐
ton
Indicates „Replace filter element“ / Press to acknowledge.
7 Switch Pump operating mode “Remote– 0 – Manual”
• Switch position “Remote”: Pump is controlled at LOP
• Switch position “0”: Pump is switched OFF
• Switch position “Manual”: Pump is started manually
8 White Signal lamp Indicates „Control voltage present”.
9 Hour meter Indicates runtime of pump.
10 Master switch
68 | Operation | MS150047/02E 2012-03