Instructions

BA LS20knx Anwendungsprogramm HM; DE,GB - 23708 - ED – V01
INSTRUCTION MANUAL ENGLISH – PAGE 2 /
2
Parameters
Parameter time switch standard
You have the possibility to activate 2 switching times (functionality like a time
switch with daily program) with a defined switching duration. Depending on the
start time and duration a switch-bit with the value “1” for ON respectively the
value “0” for OFF will be sent to the bus.
Adjustments / Description
Values
Time switch
Inactive/active
2nd switching time
Inactive/active
1
st
switching time: Switch on from [hour], [minute]
00:00 23:59
1
st
switching time: Switch on to [hour], [minute]
00:00 23:59
2
nd
switching time: Switch on from [hour], [minute]
00:00 23:59
2
nd
switching time: Switch on to [hour], [minute]
00:00 23:59
Parameters
Parameter light control
You have the possibility to send the lux value to the bus and/or to activate a light
control: lux switching (functionality like a twilight switch). Depending on your
parameter settings (Lux threshold / -hysteresis / -delay) the light control works
like a twilight switch and sends a switching bit or a scene to the bus when
reaching the lux thresholds. Additionally you have the option to activate an Extra
time switch. With this function you can program further switching times (OFF /
ON) with an adjustable duration (e.g. for energy saving solutions).
LUX LOGIC:
LUX THRESHOLD: Set the thresholds for the lux switching (ON / OFF).
FURTHER LUX THRESHOLD: You can set a further lux threshold.
LUX DELAY ON or OFF: It is possible to set a delay to avoid undesirable
switching due to disturbing light sources, e.g., car lights.
LUX HYSTERESIS: It is possible to set a hysteresis to avoid undesirable
switching due to disadvantageous positioning of the sensor, e.g., close to a
yard light.
Adjustments / Description
Values
Send measurement value
never, on query, on query and automatic/cyclic, on query
and change, on query and change and automatic/cyclic
Cycle interval for measurement value
every 30 seconds, every minute, every hour, every 6
hours, every 12 hours, at 00:00 am, at 00:02 am
Send upon x[%] change of measured value
1 50
Lux switching
Inactive/active
Light control depending on internal measurement or external bus value
Measurement value (intern), Bus (extern)**
Lux logic
ON at darkness / OFF at brightness,
OFF at darkness / ON at brightness
Threshold 2
Inactive/active
Extra time switch
Inactive/active
Settings for threshold 1 / treshold 2:
Threshold in [lux]
1 220.000 Lux
Hysteresis in [%]
0 50
Delay darkness in [s]
0 3600
Delay brightness in [s]
0 3600
Switching bit or scene
Switching bit, scene
Scene number for switching on
1 64
Scene number for switching off
1 64
* Enable blocking object
No/Yes
* Behaviour of blocking object
Block on 1 / Block on 0
* Condition after reset
Released / Blocked
* Behaviour when released
No action / Send current value
* Behaviour when blocked
No action / Send telegram
* Telegram when blocked
0/1 or scene number 1-64
Switch OFF
Inactive/active
Switch off from [hour], [minute]
00:00 23:59
Switch off to [hour], [minute]
00:00 23:59
Switch ON
Inactive/active
Switch on from [hour], [minute]
00:00 23:59
Switch on to [hour], [minute]
00:00 23:59
* Functions available in ETS application program LS 20.00 knx Version 4.0, only in combination with hardware manufactured in CW16/2017 or later.
** Definition „Receiver (internal) / Measurement value (internal)“: If „Receiver (internal)“ or „Measurement value (internal)“ is selected
the measurements provided by the LS20.00knx will be used and will also be send to the bus!
Definition „Bus (external)“: If „Bus (external)“ is selected the values provided from the bus will be used but still the measured
values of the LS20.00knx will be send to the bus!