Installation Instructions

TECHNICAL MANUAL GS 4x.10 KNX ENGLISH
42
13.2.1.2 Dimming
Designation
Options
Description
Switching/
Dimming sensor
Dimmer /
switch
Selection of operating mode as dimmer / switch.
Long actuation
from … in s
0,3 to 10,0 seconds
Configuration of time before input signal is registered as a “long actuation”.
At short actuation
(switching):
On
Off
Switchover
Inactive
Selection of value to be sent upon short actuation.
At long actuation
(dimming direction):
More brightness
Less brightness
Switchover
Switchover, after switching brighter
Switchover, after switching darker
Selection of value to be sent upon long actuation.
Dimmer
Selection of operating mode as dimmer only.
Input is being
actuated
Closed
Opened
Definition of function of input either as NO or NC contact.
At actuation:
dimming direction
More brightness
Less brightness
Switchover
Switchover, after switching brighter
Switchover, after switching darker
Selection of value to be sent upon actuation.
Dimming
procedure
Start / Stop
Steps
Brightness change per
sent telegram
1,56%, 3,13%, 6,25%, 12,5%,
25%, 50%, 100%
Selection of desired dimming procedure.
Possibility of choosing start/stop or steps.
Telegram repeated
every … s
0,3 to 10,0 seconds
By changing the telegram repetition time, the dimming speed can be varied.
Debouncing time
10 to 150 ms
Definition of debouncing time for the input.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.