TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Technical manual GS 4x.10 knx Application description – air quality sensor & control General Information The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system. The device is intended for use in accordance with the defined technical data.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Table of contents General Information ................................................................................................................................................................................................................................................................................................................................... 1 Application program ........................................................................................
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Application program Manufacturer: Program name: Installation: Hugo Müller GmbH & Co KG, Sturmbühlstraße 145-149, D-78054 VS-Schwenningen GS 4x.10 knx Add the device to your device list and open a new project. You can download the ETS database on our webpage: http://www.hugo-mueller.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Overview parameters Parameters Subcategory parameters Description Global settings Global settings Send „in operation “(incl. cycle time), request status (active/inactive, request with…), send delay after bus voltage recovers in seconds. CO2 CO2 sensor Settings CO2-sensor: Enable – disable, send measured values, CO2 offset adjustment, notification of sensor error, external value enabled/disabled.
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 24 RFR: Control value level 3 (switching object) Object function output C - - T - 1 Bit switching 24 RFR: Control value level 3 (priority) output C - - T - 2 Bit priority switching 25 RFR: Base set point [%] input C - W - - 2 Bytes humidity (%) 26 RFR: Base set point (1 Byte) [%] input C - W - - 1 Byte percent (0...
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 54 RTR: Control value main level heating Object function output C - - T - 1 Bit switching 55 RTR: Control value extra level heating output C - - T - 1 Byte counter pulses (0...255) 55 RTR: Control value extra level heating output C - - T - 1 Byte percent (0...
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 81 E1 Blinds UP/DOWN Object function output C R W T U C - - T - 1 Bit up/down 81 E1 Switch (event 0) output C - - T - 1 Bit switching 81 E1 Priority (event 0) output C - - T - 2 Bit priority switching 81 E1 1-Byte value (-128...127) (Event 0) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 81 E1 1-Byte value (0...
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 82 E1 4-Byte value (0...4.294.967.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 88 E1 ZZ: Reverse direction Object function input C - W - - 1 Bit Boolean 88 E1 Send when below threshold input C - W - - 1 Byte counter pulses (0...
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 102 E2 priority (Event 1) Object function output C R W T U C - - T - 2 Bit priority switching 102 E2 1-Byte value (-128...127) (Event 1) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 102 E2 1-Byte value (0...255) (Event 1) output C - - T - 1 Byte counter pulses (0...255) 102 E2 Scene (Event 1) output C - - T - 1 Byte scene control 102 E2 2-Byte value (-32.768...32.
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 122 E3 4-Byte value (0...4.294.967.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 141 E4 Switch (event 0) Object function output C R W T U C - - T - 1 Bit switching 141 E4 Priority (event 0) output C - - T - 2 Bit priority switching 141 E4 1-Byte value (-128...127) (Event 0) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 141 E4 1-Byte value (0...255) (Event 0) output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 142 E4 ZZ: Counter reading 1-Byte-value Object function output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Number Name Objekt size Data type 161 E5 switching level 1 Object function output C R W T U C - - T - 1 Bit switching 161 E5 switching 1 actuation output C - - T - 1 Bit switching 161 E5 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 161 E5 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 1. Global Settings (Picture shows modified parameters) Designation Send in operation Request status Send delay after bus voltage recovery …s Options Inactive Sends „0“ Sends „1“ Inactive Active Description No function. „In operation“ (0 or 1) will be send in the configured cycle time (see next parameter).
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 2. CO2 Sensor Designation CO2 Sensor Options Inactive Active Error CO2 sensor Send CO2 value when changing Send CO2 value cyclically Value offset -500 to +500 ppm External value Inactive Active Percentage: notify don’t notify Inactive If change above 10 – 500 ppm Inactive Every minute – once a day With xx% proportion Description CO2 sensor disabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 3.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 3.1 Switching commands / priority CO2 – Thresholds 1 / 2 / 3 Designation CO2 threshold 1/2/3 Options 400 to 1500 ppm Description Definition of threshold 1, 2 or 3 for the CO2 value. Switching command below threshold 1/2/3 off on Definition of the switching command below threshold 1/2/3. Switching command above threshold 1/2/3 off on Definition of the switching command above threshold 1/2/3.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 3.2 PI-control for CO2 Designation Set point Options 400 to 2000 ppm Description Definition of the setpoint. Proportional band 100 to 2000 ppm Definition of the proportional band. Reset time (15…240 min.) 15 to 240 Min. Definition of the reset time. Min. control value 0% to 95% Definition of the minimal control value. The control value is limited to this minimum value. Max. control value 5% to 100% Definition of the maximum control value.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 4. Relative humidity sensor Designation Relative humidity sensor Options Inactive Active Error humidity sensor Send relative humidity when changing Send relative humidity cyclically Value offset External value notify don’t notify Disabled If change above 1% – 25% Disabled Every minute – once a day -5% to +5% ppm Inactive Active Percentage: With xx% proportion Description Relative humidity sensor disabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 5.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 5.1 Switching commands and priority relative humidity control – Threshold 1 / 2 / 3 Designation rF threshold 1/2/3 Switching command below threshold 1/2/3 Options 20% to 50% Description Definition of threshold 1, 2 or 3 for the relative humidity value. off on If measured value is below threshold 1/2/3, switching command will not be send. If measured value is below threshold 1/2/3, switching command will be send.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 5.2 PI control for relative humidity Designation Set point Options 10% to 95% relative humidity Description Definition of the setpoint. Proportional band 10% to 40% relative humidity Definition of the proportional band. Reset time 15 to 240 min. Definition of the reset time. Min. control value 0% to 95% Definition of the minimal control value. The control value is limited to this minimum value. Max.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 6. Temperature Sensor Designation Temperature Sensor Options Disabled Enabled Description Temperature sensor disabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 7. Temperature Alarme Designation Frost alarm Options Disabled Enabled Frost alarm when temperature Send frost alarm when change of status Send frost alarm cyclically Heat alarm Disabled Enabled Heat alarm when temperature Send heat alarm when change of status Send heat alarm cyclically < 1 °C to < 10 °C Description No function.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 8. Temperature control 8.1 Temperature control – heating and cooling PI control: A PI control is a constant control that comprises a proportional part (P-part) and an integral share (I-share). The size of the P-part is indicated in Kelvin, the I-share in minutes. At a constant PI control, the manipulated variables are operated in proportional steps up to a maximum value.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 8.2 Temperature control – General Designation Blocking object heating mode: enable Options Disabled Description Blocking object disabled. Enabled Blocking object cooling mode: enable Disabled If the blocking object is activated, the reception of an external object can prevent the sending of the manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not heat if a window is open). Blocking object disabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 8.3 Temperature control – Set points Designation Comfort temperature Setback of standby heating and increment of standby cooling Setback of eco heating and increment of eco cooling Interval to main level heating and cooling Options 18° to 30°C 0 K to 10 K In 0,1 °C Steps In 0,1 K Steps Description Definition of the comfort temperature. Definition of the difference to the comfort temperature in Kelvin.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 8.4 Temperature control – Main level and extra level heating / cooling (Picture shows main level heating, PI control with output: PWM) Designation Control type Options PI control Proportional band Reset time Control value output format PWM cycle Min.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 9. Dew point Temperature Designation Dew point sensor Send dew point temperature when changing Send dew point temperature cyclically Options Disabled Enabled Disabled If change above … Disabled 0,1 K bis 10 K jede Minute - einmal am Tag Description No function. Sending of the recent condition. No function. If there is a change the recent control value is sent. No function. Cyclic sending of the recent control value.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 10. Dew point Alarm Designation Dew point alarm Options Disabled Enabled Dew point alarm advance Dew point alarm hysteresis (symmetrical) Send dew point alarm when change of status Send dew point alarm cyclically Type of telegram for dew point alarm Without 1K to 5K Without hysteresis Hysteresis value when dew point alarm value at the end of dew point alarm Description No function.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 11. Air pressure sensor Designation Air pressure sensor Options Disabled Enabled Description Temperature sensor disabled. Error air pressure Sensor Send absolute air pressure when changing Send absolute air pressure cyclically Send relative air pressure when changing Send relative air pressure cyclically Height [m. a. s. l.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 12. VAV control Function of the VAV control: The highest value of all activated PI controls of the values from CO2, relative humidity and temperature is sent in one object.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13. Inputs 13.1 General Designation Limit number of telegrams Options Inactive Active Maximum number of sent telegrams Maximum number of sent telegrams per Description No function. Number of telegrams to be sent is limited to the configured maximum. 1 to 255 Maximum number of telegrams to be sent. 50 milliseconds to 60 seconds Base for number of telegrams.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2 E1 – E5 General Designation Designation Function Options Inactive Binary input (available for E1-E5) Analogue input (E1 only) External temperature sensor (E4 only) Switching / Alarm Dimming Blind Value Scene Switching sequences Multiple operation Pulse counter Description Possibility to name each input individually. Input disabled. Available for inputs E1 to E5 (in total up to 5x). Definition of the desired use each specific input.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1 E1 – E5 as binary inputs 13.2.1.1 Switching/Alarm function (Picture shows input 1, with function as binary input. Configuration windows for inputs E2…E5 are similar). Description of functions and parameters see next page.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH Designation Switching / alarm sensor Differentiation between short and long actuation Options Switch Alarm Inactive Active Enable object „start event 0/1“ Inactive Active Reaction in case of event 0 Reaction in case of event 1 Cyclical sending Inactive Active Debouncing time… in ms Enable object Inactive „disable“ Active Description Communication object type DPT 1.001 Communication object type DPT 1.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.2 Dimming Designation Switching/ Dimming sensor Options Dimmer / switch Description Selection of operating mode as dimmer / switch. Long actuation from … in s At short actuation (switching): At long actuation (dimming direction): Dimmer Dimming procedure Debouncing time Enable object „disable“ Start / Stop Steps Inactive Active 0,3 to 10,0 seconds Configuration of time before input signal is registered as a “long actuation”.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.4 Value / forced operation Description of parameters see next page.
TECHNICAL MANUAL GS 4x.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.5 Scene Designation Input is being actuated Scene number at actuation Save scene Options Closed Opened 1…64 No At long actuation Description Definition of function of input either as NO or NC contact. Selection of the scene number to be transmittet on actuation of input. Long actuation from …s With object value= 1 At long actuation and object value= 1 Debouncing time Enable object „disable“ 10 to 150 ms Inactive Active Scenes cannot be saved.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.6 Switching sequences * Information - switching sequence type = „activate/deactivate (several buttons)“: When using above mentioned option, two binary inputs are to be configured as “switching sequences”. One of these inputs has to be configured as „direction at actuation“ = switch up, the other input has to be configured as “switch down”.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.7 Multiple operation Designation Input is being actuated Max. number of actuations Sent value Update and send at actuation Maximum time between two actuations … in s Additional object for long actuation Debouncing time Enable object „disable“ Options Closed Opened 1…4 On Off Switchover Inactive Description Definition of function of input either as NO or NC contact.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.8 Pulse counter Designation Data type (main counter) Limit value 1 Limit value 2 Counting type Number of input pulses for a counting pulse Counter reading change per counting pulse Send counter reading at download, ETS reset and bus voltage recovery Send counter reading at change Send counter reading cyclically Save counter reading Options 1-Byte value 2-Byte value 4-Byte value Range depending on selected data type. Range depending on selected data type.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.1.8.1. Intermediate counter (with function pulse counter) Designation Data type (intermediate counter) Options 1-Byte value 2-Byte value 4-Byte value Range depending on selected data type. Limit value 1 Range depending on selected data type.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.2 Function analogue input (Only available at input E1) 13.2.2.1 E1 Voltage Designation Sensor type Lower measuring limit in % of effective range Upper measuring limit in % of effective range Output value Output value tob e sent at lower measuring limit Output value tob e sent at upper measuring limit Options 0-10 V 1-10 V 0…100% 0…100% 1-Byte 2-Byte 4-Byte Range depending on selected data type. Range depending on selected data type.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.2.2 E1 Output Designation Filters Send output value Enable object „disable“ Options Inactive Low (mean of 4 measurements) Medium (mean of 16 measurements) High (mean of 64 measurements) Upon request In case of change Cyclically In case of change and cyclic Output value is sent from 1…100% x% change in output range Output value is sent every … s 5 seconds … 24 hours Inactive Active Description Filter disabled. Filter active with minimum filter function.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.2.3 E1 Threshold value Designation Use threshold value Options Inactive Active Tolerance band lower limit in % of output range Tolerance band upper limit in % of output range Limit value changeable via bus Data type of threshold value object Send if threshold value undershot Send if threshold value exceeded Minimum duration of overshoot Minimum duration of overshoot 0…100% Description Function disabled. Function enabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.2.4 E1 Output threshold value Designation Send threshold value Options In case of change In case of change and cyclic Description Send threshold only in case of change. Send if threshold value undershot, every… Send if threshold value exceeded, every… 5 seconds … 24 hours Send threshold in case of change as well as cyclically (adjustable cycle).
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.3 Function external Temperature sensor (input E4/5 only) Please Note: When using input E4 as temperature sensor, E5 cannot be used as separate input. 13.2.3.1 E4 General Designation E4/5 Temperature function Options Temperature Floor heating thermal limiter Description Connection of an external temperature sensor. Connection of an external floor heating thermal limiter (sensor).
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.3.2 E4/5 External temperature sensor / floor heating thermal limiter Designation Temperature sensor type Temperature offset in K Line fault compensation Options PT1000 TF06 -5,0…+5,0 K None Length Description Selection of the connected temperature sensor type. Adjustable offset for the temperature sensor value. Function disabled.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.3.3 E4/5 Output Designation Filters Send output value Enable object „disable“ Options Inactive Low (mean of 4 measurements) Medium (mean of 16 measurements) High (mean of 64 measurements) Upon request In case of change Cyclically In case of change and cyclic Output value sent from 1…200 a change of x 0,1°C Output value is sent every 5 seconds… 24 hours Inactive Active Description Filter disabled. Filter active with minimum filter function.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.3.
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 13.2.3.5 E4/5 Output threshold value 1 / 2 (only if E4 general temperature function = Temperature) Designation Send threshold value object Options In case of change In case of change and cyclic Description Send threshold only in case of change. Send if threshold value undershot, every 5 seconds … 24 hours Send if threshold value exceeded, every 5 seconds … 24 hours Send threshold in case of change as well as cyclically (adjustable cycle time). 13.2.3.