7.  Temperature Alarme 
Designation 
Options 
Description 
Frost alarm 
Disabled 
Enabled 
No function. 
If the alarm function is activated an alarm in the form of an object is sent when the temperature 
falls below a defined temperature threshold for frost alarm. 
Frost alarm 
when temperature  
< 1 °C to < 10 °C 
When falling below the defined temperature the object frost alarm is sent. 
Send frost alarm  
when change of  
status 
Disabled 
Enabled 
No function. 
If there is a change the recent control value is sent. 
Send frost alarm  
cyclically 
Disabled 
Every minute – once a 
day 
No function. 
Cyclic sending of the recent control value. 
Heat alarm 
Disabled 
Enabled 
No function. 
If the alarm function is activated an alarm in the form of an object is sent when the temperature 
exceeds a defined temperature threshold for heat alarm. 
Heat alarm when  
temperature  
> 20 °C to > 30 °C 
When exceeding the defined temperature, the object heat alarm is sent. 
Send heat alarm  
when change of status 
Disabled 
Enabled 
No function. 
If there is a change the recent control value is sent. 
Send heat alarm  
cyclically 
Disabled 
Every minute – once a 
day 
No function. 
Cyclic sending of the recent control value. 