8.2  Temperature control – General 
Designation 
Options 
Description 
Blocking object  
heating mode: enable 
Disabled 
Enabled 
Blocking object disabled. 
If the blocking object is activated, the reception of an external object can prevent the sending of the 
manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not heat if a 
window is open). 
Blocking object  
cooling mode: enable 
Disabled 
Enabled 
Blocking object disabled. 
If the blocking object is activated, the reception of an external object can prevent the sending of the 
manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not heat if a 
window is open). 
Blocking object extra level 
heating: enable 
Disabled 
Enabled 
Blocking object disabled. 
If the blocking object is activated, the reception of an external object can prevent the sending of the 
manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not cool if a 
window is open). 
Blocking object extra level 
cooling: enable 
Disabled 
Enabled 
Blocking object disabled. 
If the blocking object is activated, the reception of an external object can prevent the sending of the 
manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not cool if a 
window is open). 
Heating demand  
for display 
Disabled 
Enabled 
Status object disabled. 
This object is a status object to send the status of heating (active or not). It can be used to visualize the 
status on a display. 
Cooling demand  
for display 
Disabled 
Enabled 
Status object disabled. 
This object is a status object to send the status of cooling (active or not). It can be used to visualize the 
status on a display. 