Installation Instructions
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 
4 
Overview parameters 
Parameters 
Subcategory parameters 
Description 
Global 
settings 
Global settings 
Send „in operation “(incl. cycle time), request status (active/inactive, request with…), send delay after bus voltage recovers in seconds. 
CO
2
CO
2 
sensor 
Settings CO
2
-sensor: Enable – disable, send measured values, CO
2
 offset adjustment, notification of sensor error, external value 
enabled/disabled. 
CO
2
 control 
Settings CO
2
-control: Type (inactive, 1-/2-/3-step, PI), output format, send on change / send cyclically, hysteresis (symmetrical). 
Threshold 1,2,3, switching command above / below threshold, control value, blocking object 
Relative 
humidity 
sensor 
Relative humidity sensor 
Settings humidity sensor: Enable – disable, send measured values, offset adjustment, notification of sensor error, external value 
enabled/disabled. 
Relative humidity control 
Settings humidity control: Type (inactive, 1-/2-/3-step, PI), output format, send on change / send cyclically, hysteresis (symmetrical). 
Threshold 1,2,3, switching command above / below threshold, control value, blocking object 
Temperature 
Temperature sensor 
Settings temperature sensor: Enable – disable, send measured values, offset adjustment, notification of sensor error, external value 
enabled/disabled. 
Temperature alarms 
Settings frost- and/or heat alarms: Enable – disable, send measured values. 
Temperature control 
Settings temperature control: Type (inactive, heating, cooling, heating & cooling), different control values (extra cooling level & guide). 
Dew point 
Dew point temperature 
Settings dew point: Enable – disable, send measured values. 
Dew point alarm 
Settings dew point alarm: Enable – disable, send measured values., hysteresis (symmetrical), switching command on alarm. 
Air pressure 
Air pressure sensor 
Settings Air pressure-Sensor: Enable – disable, send measured values, notification of sensor error, elevation. 
VAV control 
Settings 
Settings VAV control: Enable – disable for different (already configured) PI controls, send control values according to defined parameters 
and values. 
Inputs 
General 
E1…E5 general 
E1…E5 parameters 
Limitation of number and interval of telegrams to be send 
Labeling of inputs, selection of function as analogue-/binary-/temperature input (functions depending on input) 
Binary input: switching/alarm, dimming, blinds/shutters, value, scene, switching sequences, multiple operation, pulse counter 
Analogue input (E1 only): Voltage, upper/lower measuring limits, output value, threshhold, limits changeable via bus 
Temperature sensor input (E4/5 only): Function temperature / temperature limiter floor heater, sensor type, offset, error compensation, 
threshold 1, threshold 2 