13.2.1.6  Switching sequences 
Designation 
Options 
Description 
Input is being  
actuated 
Closed 
Opened 
Definition of function of input either as NO or NC contact. 
Number of steps 
2…5 
Definition of number of total steps 
Switching sequence 
type 
Activate/deactivate 
(one button) 
Activate/deactivate 
(several buttons)* 
All possibilities 
(„Gray-Code“) 
Direction 
at actuation 
Switch up 
Switch down 
Debouncing time  
10 to 150 ms 
Definition of debouncing time for the input. 
Activate minimum 
signal duration 
Inactive 
Active 
At contact opening  
in value x 0,1 s 
At contact closing  
in value x 0,1 s 
1…65535 x 0,1 seconds 
1…65535 x 0,1 seconds 
Enable object  
„disable“ 
Inactive 
Active 
Communication object (blocking object) for input is disabled. 
Communication object (blocking object) for input is enabled. 
* Information - switching sequence type = „activate/deactivate (several buttons)“: 
When using above mentioned option, two binary inputs are to be configured as 
“switching sequences”. One of these inputs has to be configured as „direction at 
actuation“ = switch up, the other input has to be configured as “switch down”. In 
order to assure synchronous function of these two inputs / sequences, the two 
communication objects „actuating number“ of the two inputs have to be assigned to 
the same group address.  
Example:  
Use of E1 for switching up, E2 for switching down 
E1 actuating number  group address 1/1/5 
E2 actuating number  group address 1/1/5 