13.2.2  Function analogue input (Only available at input E1) 
13.2.2.1  E1 Voltage 
Designation 
Options 
Description 
Sensor type 
0-10 V 
1-10 V 
Selection of the connected input signal type (0-10V oder 1-10V). Also defines the 
effective range. 
Lower measuring limit in % of  
effective range 
0…100% 
Lower measuring range limit.  
If signal is below this value, output of „1” on object „E1 out of range”. 
Upper measuring limit in % of  
effective range 
0…100% 
Upper measuring range limit.  
If signal is above this value, output of „1” on object „E1 out of range“. 
Output value 
1-Byte 
2-Byte 
4-Byte 
Selection of output value type for lower / upper measuring limit. 
Output value tob e sent at lower 
measuring limit 
Range depending on selected data type. 
Definition of output value to be sent at lower measuring limit. 
Output value tob e sent at upper 
measuring limit 
Range depending on selected data type. 
Definition of output value to be sent at upper measuring limit. 