Installation Instructions
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 
52 
13.2.2.2  E1 Output 
Designation 
Options 
Description 
Filters 
Inactive 
Low 
Medium 
High 
(mean of 4 measurements) 
(mean of 16 measurements) 
(mean of 64 measurements) 
Filter disabled. 
Filter active with minimum filter function. 
Filter active with medium filter function. 
Filter active with high filter function. 
Send output value 
Upon request 
In case of change 
Cyclically 
In case of change and cyclic 
Send value only upon request. 
Send value upon change (see following parameters).  
Send value cyclically (see following parameters). 
Send value upon change and cyclically (see following two parameters). 
Output value is sent from  
x% change in output range 
1…100% 
Applies to send „In case of change“ and „Send value upon change and cyclically“: 
Parameter for necessary change before sending the value.  
Output value is sent every … s 
5 seconds … 
24 hours 
Applies to send „cyclically“ and „Send value upon change and cyclically“: Configuration 
of interval, when value is sent. 
Enable object  
„disable“ 
Inactive 
Active 
Communication object (blocking object) for input is disabled. 
Communication object (blocking object) for input is enabled. 