Installation Instructions
TECHNICAL MANUAL GS 4x.10 KNX – ENGLISH 
53 
13.2.2.3  E1 Threshold value 
Designation 
Options 
Description 
Use threshold 
value 
Inactive 
Active 
Function disabled. 
Function enabled. 
Tolerance band lower limit  
in % of output range 
0…100% 
Configuration of lower band limit, e.g. 10% for 1 V. 
Tolerance band upper limit  
in % of output range 
0…100% 
Configuration of upper band limit, e.g. 80% for 8 V. 
Limit value changeable via bus 
Inactive 
Active 
Limit value fixed via ETS / stored in device. 
Upper / lower tolerance band can be changed via separate communication objects via 
bus. 
Data type of threshold value object 
1 Bit 
1 Byte 
2 Byte 
Selection of desired data type for the thresholds. 
Send if threshold value undershot 
Depending on 
selection of data 
type 
e.g. ON / OFF / no telegram (at 1-bit data type). 
Send if threshold value exceeded 
Depending on 
selection of data 
type 
e.g. ON / OFF / no telegram (at 1-bit data type). 
Minimum duration of overshoot 
Inactive 
5 seconds… 
24 hours 
Configurable minimum duration, before „threshold undershoot“ is sent. 
Minimum duration of overshoot 
Inactive 
5 Sek… 
24 Std. 
Configurable minimum duration, before „threshold exceeded“ is sent. 