Operation
ProStar Operator’s Manual
39
38
4.0
DIP
S
witch
S
ettings
4
-5-6
B
attery
T
ype
A
bsorp.
S
tage
(
volts)
F
loat
S
tage
(
volts)
E
qualize
S
tage
(
volts)
A
bsorp.
T
ime
(
mins)
E
qualize
T
ime
(
mins)
E
qualize
T
imeout
(
mins)
E
qualize
Equalize
Equalize
I
nterval
(
days)
Equalize
Interval
(days)
Equalize
Interval
(days)
off-off-off 1 - Sealed* 14.00 13.50
150
off-off-on 2 - Sealed* 14.15 13.50 14.40 150 60 120 28
off-on-off 3 - Sealed* 14.30 13.50 14.60 150 60 120 28
off-on-on 4- AGM/Flooded 14.40 13.50 15.10 180 120 180 28
on-off-off 5 - Flooded 14.60 13.50 15.30 180 120 180 28
on-off-on 6 - Flooded 14.70 13.50 15.40 180 180 240 28
on-on-off 7 - L-16 15.40 13.40 16.00 180 180 240 14
on-on-on 8 - Custom Custom Custom Custom Custom Custom Custom Custom
Custom Custom
Custom
* “Sealed” baery type includes gel and AGM baeries
Custom
LVD
(volts)
LVR
(volts)
Custom
12.30
13.80
12.10 13.60
11.90
13.40
11.50
13.00
11.70
13.20
11.30
12.80
11.50
12.60
Table 4.1. Battery charging settings for each selectable
battery type
Shared Settings Value Units
Absorption Extension voltage 12.50 Volts
Absorption Extension Time Absorption Time + 30 minutes
Float Exit Time-out 30 minutes
Float Cancel voltage 12.30 Volts
Equalize Time-out Equalize Time + 60 minutes
Temperature Compensation Coefficient - 30
millivolts
/ °C /
12V
Table 4.2. Battery settings that are shared between all
battery types
Absorption Extension
1:00 2:00 3:00 4:00 5:00 6:00
12.50 V
Bulk
Extended
Absorption
FloatAbsorption
Absorption Extension Voltage
time (hrs)
Figure 4-2. Absorption Extension Charging Profile
If battery voltage discharges below 12.50 Volts (25.00
Volts @ 24V) the previous night, Absorption charging
will be extended on the next charge cycle as shown
in figure 4-2 above. 30 minutes will be added to the
normal Absorption duration.