Cut Sheet

23
AFC Cable Systems, Inc. 800-757-6996 www.afcweb.com
Ordering Information
Reduced Wall Flexible Steel Conduit
Interlocking Steel Armor
Description
• Reduced Wall Flexible Steel Conduit
• High grade hot dipped zinc galvanized low carbon steel
• Interlocking design
• Corrosion resistant
Applications
• Flexible metal raceway for electrical power,
control and communication cables
• Motor leads
• Listed assemblies
• Listed wire fixtures
• Manufactured wiring systems
Product Dimensions/
Ordering Information Bend Radius
Approx. Internal External
Trade Trade Coil Reel Weight/ Diameter Diameter Bend
Product Size Size Length Length 100 feet (min/max) (min/max) Radius
Code (inches) (mm) (feet) (feet) (pounds) inches inches (inches)
5501-22-00+ 3/8 12 25' 17 0.375/0.393 0.560/0.610 2
5501-24-00+ 3/8 12 50' 17 0.375/0.393 0.560/0.610 2
5501-30-00+ 3/8 12 100' 17 0.375/0.393 0.560/0.610 2
5501-42-00+ 3/8 12 250' 17 0.375/0.393 0.560/0.610 2
5501-45-00+ 3/8 12 500' 17 0.375/0.393 0.560/0.610 2
5501-60-00+ 3/8 12 1000' 17 0.375/0.393 0.560/0.610 2
5502-22-00 1/2 16 25' 27 0.625/0.645 0.860/0.920 3
5502-24-00 1/2 16 50' 27 0.625/0.645 0.860/0.920 3
5502-30-00 1/2 16 100' 27 0.625/0.645 0.860/0.920 3
5502-45-00 1/2 16 500' 27 0.625/0.645 0.860/0.920 3
5502-60-00 1/2 16 1000' 27 0.625/0.645 0.860/0.920 3
5503-22-00 3/4 21 25' 35 0.812/0.835 1.045/1.105 4
5503-24-00 3/4 21 50' 35 0.812/0.835 1.045/1.105 4
5503-30-00 3/4 21 100' 35 0.812/0.835 1.045/1.105 4
5503-45-00 3/4 21 500' 35 0.812/0.835 1.045/1.105 4
5503-60-00 3/4 21 1000' 35 0.812/0.835 1.045/1.105 4
5504-24-00 1 27 50' 51 1.000/1.040 1.300/1.380 5
5504-80-00 1 27 300' 51 1.000/1.040 1.300/1.380 5
5505-24-00 1
1
4
35 50' 63 1.250/1.300 1.550/1.630 6.25
5505-40-00 1
1
4
35 200' 63 1.250/1.300 1.550/1.630 6.25
5506-22-00 1
1
2
41 25' 76 1.500/1.575 1.850/1.950 7.50
5507-22-00 2 53 25' 100 2.000/2.080 2.350/2.450 10
5508-22-00 2
1
2
63 25' 165 2.500/ — 2.860/3.060 12.50
5509-22-00 3 78 25' 197 3.000/ — 3.360/3.560 15
5510-22-00 3
1
2
91 25' 230 3.500/ — 3.860/4.060 17.50
5511-22-00 4 103 25' 263 4.000/ — 4.360/4.560 20
NOTE: All dimensions and weights are subject to normal manufacturing tolerances.
+
CSA certified
Review NEC
®
250.118(6) for grounding requirements.
References & Ratings
• UL 1, UL 1479, File Reference E11831, CSA File Number 15035,
CSA C22.2 No. 56 (trade size 3/8 only)
• Federal Specification WW-C-566C, (now superseded by UL 1)
• NEC
®
250.118(6), 300.22(C), 348, 430.123, 501.4(B)(2), 645.5
• Cable Tray installations per NEC
®
• Environmental Air-Handling space installation NEC
®
300.22(C)
• UL Classified 1, 2 and 3-hour Through-Penetration Fire Systems
UL File R14141
LiquidTuff catalog 4/21/04 1:59 PM Page 23

Summary of content (1 pages)