of the National Electrical Code Section
310.15 and 240.4(D). Unless the equipment is marked for use at higher
temperatures the conductor shall be limited to the following per NEC 110.14(C).
60° C - When terminated to equipment for circuits rated 100 ampers or less or
marked for 14 - 1 AWG conductors.
75° C - When terminated to equipment for circuits rated over 100 ampers or marked
for conductors larger than1 AWG.
90° C - THHN dry locations and THWN wet or dry locations for ampacity adjustment
purposes using NEC section 310.15.