Cut Sheet
NM-B
• 90˚C Insulation
• With Ground Wire
• 600 Volts
1
Cerro W
ire & Cable Co., Inc.
1099 Thompson Road, SE • Hartselle, AL 35640
Phone 256.773.2522 • Fax 256.773.5849 • www.cerrowire.com
Cirtex
®
Non-Metallic Sheathed Cable
APPLICATIONS
• For use primarily in residential
wiring including branch circuits
for outlets, switches, etc
• May be installed in both exposed
and concealed work in normally
dry locations
• May be installed in air voids
of masonry block or tile walls
where these walls are not
subject to excessive moisture
or dampness
• May be installed in locations
with temperatures up to 90˚C
but with the ampacity limited
to that of 60˚C conductors
•
Added Circuit: For use primarily
in residential wiring for branch
circuits supplying outlets located
in bedrooms and other areas
• Has two seperate neutrals so
that one cable can be used to
run two circuits when sharing
of a neutral is not allowed
CONDUCTORS
• Solid conductors: Soft, uncoated
copper per ASTM-B3
• Stranded conductors: Uncoated
copper per ASTM-B3 and ASTM-B8
CONDUCTOR INSULATION
AN
D J
ACKET
• Color coded PVC (polyvinyl
chloride), rated 90˚C dry
•
Added Circuit: Color coded PVC
rated 90˚C: black, white, red and
white with red stripe.
•
Insulated conductors also jacketed
with clear nylon (polyamide)
Product Code
Number &
Package Code
w/Ground
Conductors
Ground
Wire
A
WG
Insulation
& Nylon
Thickness
Mils.
Cable
Dimension
Mils.
Ampacities
at 30˚C
P
er NEC
®
Approx. Net
Wt. lbs./m ft.
A
WG &
No. Cond.
No. of
Strands
1
47
w/Grnd
147-1462 14-2 SOL 14 19 190 x 370 15 60
147-1662 12-2 SOL 12 19 210 x 400 20 84
147-1862 10-2 SOL 10 24 230 x 480 30 128
147-4002 8-2 7 10 35 370 x 680 40 208
147-4202 6-2 7 10 35 420 x 750 55 288
147-1463 14-3 SOL 14 19 300 15 76
147-1663 12-3 SOL 12 19 335 20 109
147-1863 10-3 SOL 10 24 408 30 166
147-4003 8-3 7 10 35 515 40 260
147-4203 6-3 7 10 35 675 55 366
147-4403 4-3 7 8 45 760 70 585
147-4603 2-3 7 8 45 910 95 843
EZ-ID
®
PLUS and EZ-STRIP
®
PLUS