Cut Sheet

SEU
Type SE, Style U
600V
90°C Wet or Dry
Description:
May be used as service-entrance conductors, feeders and branch circuits where
SE cables are permitted when installed as specied by the National Electrical
Code
®
(NEC). May be used in wet or dry locations at temperatures up to 90°C.
Uninsulated conductor between two insulated conductors, parallel-laid then
wrapped in a glass-reinforced tape. Uninsulated (bare) conductor may be used for
equipment grounding where used for feeder or branch circuit applications. Gray,
sunlight-resistant PVC jacket over the complete assembly.
Materials:
Stranded conductors: Uncoated copper per ASTM B3, ASTM B8, and ASTM B787.
Insulated conductors: Type THHN/ THWN-2 insulation. Black PVC insulation with
black nylon. Rated for use up to 90°C in wet or dry locations.
Phase ID: A red stripe on insulation surface of one conductor.
Uninsulated conductor: Bare stranded copper.
Standards:
UL 83: E15119
UL 854: E11098
ASTM B3
ASTM B8
ASTM B787
Federal Specication A-A-59544
NFPA 70 (National Electrical Code
®
)
Surface Print:
Sample: TYPE SE STYLE U TYPE THHN
OR THWN-2 2 CDRS 6 AWG 1 CDR 8
AWG 600V E11098-A (UL)
Service Entrance Cable
Electrical Distribution 800.523.3869
©2019 Cerrowire Rev 06/2020
A Marmon/Berkshire Hathaway Company
Features:
* See NEC
®
Table 310.15(B)(16).
** For termination to equipment circuits rated 100 amperes or less, or marked for 14 AWG through 1 AWG conductors. See NEC
®
110.14(C)(1).
*** For termination to equipment circuits rated over 100 amperes or marked for conductors larger than 1 AWG. See NEC
®
110.14(C)(1).
**** Dry or wet locations, for ampacity correction and adjustment purposes.
***** For dwelling units, conductors are permitted at listed ampacities for 3-wire, single-phase service or feeder conductors that supply the total load.
See NEC
®
310.15(B)(7).
Data are approximate and subject to normal manufacturing tolerances.
It is the sole responsibility of the end user to determine suitability of this product for its intended use and application.
Allowable Ampacities*
8-8-8 7 .400 x .710 40 50 55
––––
241
6-6-8 7 .400 x .770 55 65 75
––––
313
6-6-6 7 .400 x .790 55 65 75
––––
348
4-4-6 7 .470 x .950 70 85 95 100 486
4-4-4 7 .470 x 1.030 70 85 95 100 533
3-3-5 7 .500 x 1.040 85 100 115 110 588
2-2-4 7 .565 x 1.100 95 115 130 125 721
2-2-2 7 .565 x 1.200 95 115 130 125 802
2/0-2/0-2/0 19 .900 x 1.400 145 175 195 200 1412
Approx. Overall
Dimensions (in)
Conductor Size
( AWG)
Stranding
Net Weight
(Lbs/MFt)
60°C
**
75°C
***
90°C
****
Dwelling
*****