Cut Sheet

1-ONE
2-TWO
Tray & Power Cables
Phoenix, AZ Culloden, WV Houston, TX
877-623-9473 800-624-3572 800-231-9473
servicewire.com
Manufacturing quality. Delivering service.
33
SE-U
XHHW-2/PVC
Service Entrance
600 Volt Copper
Description:
2 conductors, stranded, insulated with heat and moisture resistant
crosslinked polyethylene (type XHHW-2) and phase identied.
Cabled together with bare copper ground conductor. Cable core
covered with ame retardant binder tape and overall grey PVC
jacket.
Standards:
UL 44 and UL 854
ICEA S-95-658/NEMA WC70
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
Color Code: Method 4
RoHS Compliant
Part
Number
Size
AWG
Strand
(no.)
Insulation
Thickness
(mils)
Grounding
Conductor
(AWG)
Jacket
Thickness
(mils)
Diameter
Overall
(inch)
Approx.
Net Weight
(lb/1000')
Ampacity*
(30°C ambient)
90°C Wet/Dry
TWO CONDUCTOR
SEU8/2G8
8 7 45 8 30 0.67 226 55
SEU6/2G8
6 7 45 8 30 0.75 300 75
SEU6/2G6
6 7 45 6 30 0.77 330 75
SEU4/2G6
4 7 45 6 30 0.87 442 95
SEU4/2G4
4 7 45 4 30 0.90 492 95
SEU3/2G4
3 7 45 4 30 0.96 560 115
SEU3/2G3
3 7 45 3 30 0.97 595 115
SEU2/2G4
2 7 45 4 30 1.02 664 130
SEU2/2G2
2 7 45 2 30 1.06 744 130
SEU1/2G1
1 19 55 1 30 1.10 920 145
SEU1/02G1/0
1/0 19 55 1/0 30 1.20 1,238 170
SEU2/02G2/0
2/0 19 55 2/0 30 1.32 1,413 195
SEU3/02G3/0
3/0 19 55 3/0 30 1.42 1,757 225
SEU4/02G4/0
4/0 19 55 4/0 30 1.61 2,175 260
* PER NEC TABLE 310-16
NOTE: The data shown is approximate and subject to standard industry tolerances.

Summary of content (1 pages)