Cut Sheet

Impedance Data
Quadruplex Overhead Service Drop Cable
Phase Neutral 25°C 50°C 75°C X1
#4 #4 0.4227 0.4645 0.5064 0.0290
#2 #2 0.2655 0.2929 0.3182 0.0280
1/0 1/0 0.1671 0.1837 0.2002 0.0273
2/0 2/0 0.1326 0.1456 0.1587 0.0266
3/0 3/0 0.1053 0.1157 0.1259 0.0264
4/0 4/0 0.0835 0.0917 0.1001 0.0260
336.4 4/0 0.0527 0.0578 0.0629 0.0240
336.4 336.4 0.0527 0.0578 0.0629 0.0251
AC RESISTANCE
(OHMS/1000 FT.)
INDUCTIVE REACTANCE
(OHMS/1000 FT.)
Triplex Overhead Service Drop Cable
AC RESISTANCE
(OHMS/1000 FT.)
INDUCTIVE REACTANCE
(OHMS/1000 FT.)
NOTES: Neutral sizes are ACSR or AAAC
Soil (RHO) Resistivity = 100
NOTES : Neutral sizes are ACSR or AAAC
Soil (RHO) Resistivity = 100
Aluminum Multiplexed
Overhead Service and
Secondary Cables
Phase Neutral 25°C 50°C 75°C X1
#6 #6 0.6725 0.7392 0.8059 0.0287
#4 #6 0.4227 0.4645 0.5064 0.0268
#4 #4 0.4227 0.4645 0.5064 0.0286
#2 #4 0.2655 0.2929 0.3182 0.0258
#2 #2 0.2655 0.2929 0.3182 0.0276
1/0 #2 0.1671 0.1837 0.2002 0.0252
1/0 1/0 0.1671 0.1837 0.2002 0.0269
2/0 2/0 0.1326 0.1456 0.1587 0.0264
3/0 3/0 0.1053 0.1157 0.1259 0.0261
4/0 4/0 0.0835 0.0917 0.1001 0.0257
336.4 4/0 0.0527 0.0578 0.0629 0.0233
336.4 336.4 0.0527 0.0578 0.0629 0.0248