Cut Sheet

APPLICATION:
THHN / THWN-2 / T90 building wire is intended for general
purpose applications, and is permitted for use in new
construction and rewiring of 600 volt applications. The cable’s
conductors may be used in wet or dry locations at temperatures
not to exceed 90°C. The cable should be installed without the
application of pulling lubricant.
CONDUCTORS:
• Compact bare AA-8000 series aluminum, with Class B
stranded per ASTM
INSULATION:
Low coefficient of friction (“slick”), abrasion, heat and
moisture resistant Polyvinyl Chloride (PVC)
Aluminum THHN/THWN-2/T90 600V
PVC/Nylon Insulation
#1010-01
ALUMINUM BUILDING WIRE
1-800-945-5542
www.PriorityWire.com
JACKET:
• A clear abrasion, heat, moisture resistant and low coefficient
of friction nylon jacket. Standard stock colors include: black,
red, blue, white, brown, orange, yellow, gray, purple and green
STANDARDS:
UL 83, UL 1685, cUL
CSA C22.2 No. 75
1/0 & larger are rated for CT use
NEC & CEC
NEMA WC-70 / ICEA S-95-658
ASTM B800, B801, B836
Federal Specification AA-59544
VW-1/FT1 Flame Test
Sunlight resistant / Gas and Oil Resistant II
All values are nominal and subject to correction.
**Ampacities shown are for general use as specified by the National Electrical Code 2017 Edition, Section 310.15 and 240.4(D). Unless the
equipment is marked for use at higher temperatures, the conductor ampacities shall be limited to the follwing per NEC 110.14(C): 60°C - When
terminated to equipment for circuits rated 100 amperes or less marked for 14 through 1 AWG conductors. 75°C - When terminated to equipment for
circuits rated over 100 amperes or marked for conductors larger than 1 AWG. 90°C - THHN dry locations and THWN wet or dry locations for ampacity
adjustment purposes using NEC section 310.15.
©2021 Priority Wire & Cable
10-2021
Part Number
Conductor
Size
Conductor
Diameter
Insulation
Thickness
Jacket
Thickness
Overall
Diameter
Net
Weight
Ampacity**
AWG/KCM inches inches inches inches lbs/kft at 60°C at 75°C at 90°C
8-01AL-THHN 8 0.134 0.030 0.005 0.204 27 35 40 45
6-01AL-THHN 6 0.169 0.030 0.005 0.239 38 40 50 55
4-01AL-THHN 4 0.213 0.040 0.006 0.305 62 55 65 75
2-01AL-THHN 2 0.268 0.040 0.006 0.360 91 75 90 100
1-01AL-THHN 1 0.299 0.050 0.007 0.413 117 85 100 115
1/0-01AL-THHN 1/0 0.335 0.050 0.007 0.450 141 100 120 135
2/0-01AL-THHN 2/0 0.378 0.050 0.007 0.490 172 115 135 150
3/0-01AL-THHN 3/0 0.423 0.050 0.007 0.537 210 130 155 175
4/0-01AL-THHN 4/0 0.476 0.050 0.007 0.589 257 150 180 205
250-01AL-THHN 250 0.520 0.060 0.008 0.656 311 170 205 230
300-01AL-THHN 300 0.571 0.060 0.008 0.706 365 190 230 260
350-01AL-THHN 350 0.614 0.060 0.008 0.752 418 210 250 280
400-01AL-THHN 400 0.657 0.060 0.008 0.795 471 225 270 305
500-01AL-THHN 500 0.736 0.060 0.008 0.872 576 260 310 350
600-01AL-THHN 600 0.816 0.070 0.009 0.971 700 285 340 385
700-01AL-THHN 700 0.877 0.070 0.009 1.035 804 315 375 425
750-01AL-THHN 750 0.909 0.070 0.009 1.066 856 320 385 435
900-01AL-THHN 900 0.999 0.070 0.009 1.139 1013 355 425 480
1000-01AL-THHN 1000 1.059 0.070 0.009 1.218 1117 375 445 500